| Plan Review Notes For Permit 01040455 |
| Permit Number |
01040455 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-17 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE | | | MISSING OUTLETS REQ`D BY NEC AND LOCAL | | | CODE. 210-50 | | | | | | 2)NOTE: PLEASE NOTE MISSING SHOW WINDOW | | | OUTLETS PER 210-62 | | | | | | | | | 3)NOTE: PLEASE NOTE THAT NO LOAD | | | CALCUALTIONS WERE SUBMITTED FOR | | | EXSITING AND NEW LOADS BEING ADDED? | | | | | | 4)NOTE: PLEASE SHOW TRACL LIGHTING/SHOW | | | WINDOW PER 220-12A&B | | | | | | 5)NOTE: PLEASE NOTE THAT ALL BRANCH | | | CIRCUIT #`S ARE TO SHOWN ON PLANSAND | | | NEED TO CORRELATE WITH A SUBMITTED | | | PANELSCHEDULE. PLEASE SHOW EXISTING | | | PANEL SIZE. | | | | | | | | | 6)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS ARE TO BE SHOWN AT 125%. | | | | | | PLEASE CLARIFY PANEL SHOWN IN CLOSET? | | | DOOR?. IF CLOSET THEN PLANS NEED TO BE | | | LABELED ELEC ONLY, NO STORAGE! PER | | | 110-26AND 384-7. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|