Plan Review Notes
Plan Review Notes For Permit 01040455
Permit Number 01040455
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-17 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE
 MISSING OUTLETS REQ`D BY NEC AND LOCAL
 CODE. 210-50
  
 2)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLETS PER 210-62
  
  
 3)NOTE: PLEASE NOTE THAT NO LOAD
 CALCUALTIONS WERE SUBMITTED FOR
 EXSITING AND NEW LOADS BEING ADDED?
  
 4)NOTE: PLEASE SHOW TRACL LIGHTING/SHOW
 WINDOW PER 220-12A&B
  
 5)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUIT #`S ARE TO SHOWN ON PLANSAND
 NEED TO CORRELATE WITH A SUBMITTED
 PANELSCHEDULE. PLEASE SHOW EXISTING
 PANEL SIZE.
  
  
 6)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%.
  
 PLEASE CLARIFY PANEL SHOWN IN CLOSET?
 DOOR?. IF CLOSET THEN PLANS NEED TO BE
 LABELED ELEC ONLY, NO STORAGE! PER
 110-26AND 384-7.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372