| 2001-06-25 00:00:00 | SECOND CHECKLIST: |
| | 1-MISSING ORIGINAL PERMIT APPLICATION. |
| | 2-ENTRY DOOR TO HAVE 32" MIN. CLEAR |
| | OPENING. TABLE 1004 SBC 1997. |
| | DOOR BY CABANA BATH IS NOT THE MAIN |
| | EGRESS. |
| | 3-SPECIFY SAFETY GLASS WHERE REQUIRED BY |
| | SEC 2405.2 SBC 1997. NEW EGRESS WINDOW |
| | IS WITHIN THE 24" RADIOUS OF DOOR. |
| | 4-ARCHITECT TO CLEARLY SPECIFY ON DWGS |
| | THAT GLASS BLOCK @ ZERO LOT LINE NEEDS |
| | TO BE ONE HOUR FIRE RATED. TABLE 600. |
| | 5-ARCHITECT TO UPDATE SHEET C-1. SEE |
| | COMMENTS. |
| | 6-REVISE STORM PANEL INSTALLATION SCHED: |
| | A)SEE MASONRY OPENINGS SPECIFIED BY THE |
| | ARCHITECT AND REVISE ACCORDINGLY. |
| | B)INSTALLATION SCHEDULE ANCHOR SPACING |
| | DOESN'T MATCH THE SPACING SCHEDULE AS |
| | SHOWN ON SHEETS 5 & 6 OF APPROVED |
| | DRAWINGS. |
| | -CLEARLY WRITE THE ANCHOR SPACING |
| | ACCORDING TO THE TYPE OF STRUCTURE TO |
| | BE ATTACHED TO: CONC. OR CONC. BLOCK. |
| | 7-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ENTRY DOORS (NOT LEGIBLE). |
| | B)ARCHITECT TO REVISE DWGS IF CABANA |
| | DOOR DOESN'T HAVE TRANSOM ABOVE. |
| | C)SLIDING GLASS DOORS W/ TRANSOM ABOVE |
| | SINGLE ASSEMBLY. PRODUCT APPROVAL |
| | SUBMITTED IS FOR WINDOWS ONLY. |
| | D)MISSINGDWGS FOR 16'-0" GARAGE DOOR. |
| | E)DWGS OF GLASS BLOCK PRODUCT APPROVAL |
| | ARE NOT LEGIBLE. |
| | -PROVIDE DETAILS AND SPECS FOR ONE HR |
| | FIRE RATED GLASS BLOCK ASSEMBLY. |
| | F)FIXED WINDOWS WITH SIZES AS SHOWN ON |
| | ARCHITECT'S EXTERIOR ELEVATIONS. |
| | G)BUTT GLAZING AND FIXED WINDOW BY |
| | BREAKFAST AREA. |
| | -NOTE: FOR SITE SPECIFIC ENGINEERING |
| | USE CITY SAMPLE FORM AND NEED TO BE |
| | SIGNED, SEALED AND DATED BY THE |
| | MANUFACTURER'S ENGINEER AND BY THE |
| | PROFESSIONAL OF RECORD. |
| | H)PGT ENGINEER, ROBERT L. CLARK PE, TO |
| | SIGN, SEAL & DATE LETTER AS REQUIRED |
| | BY CHAPTER 471 OF FLORIDA STATUTES |
| | WHEN SUBMITTING INFORMATION FOR |
| | PUBLIC RECORDS. |
| | 8-PROVIDE DETAIL & SPECS FOR 2X STRUCT. |
| | BUCK DETAIL. SEE DOOR PRODUCT APPROVAL |
| | NOTE: |
| | PLEASE RETURN REVIEWED SET OF DRAWINGS |
| | AFTER CORRECTIONS ARE DONE TO ORGINALS |
| | IN ORDER TO EXPEDITE THE REVIEW. THIS |
| | WAS NOT DONE FOR THIS SUBMITTAL, THERE- |
| | FORE I HAD TO RE-REVIEW THE ALL SET |
| | AGAIN. |