Plan Review Notes
Plan Review Notes For Permit 01040436
Permit Number 01040436
Review Stop R
Sequence Number 3
Notes
Date Text
2001-06-27 00:00:00SECOND CHECKLIST:
 1-MISSING ORIGINAL PERMIT APPLICATION.
 2-ENTRY DOOR TO HAVE 32" MIN. CLEAR
 OPENING. TABLE 1004 SBC 1997.
 REAR DOOR BY CABANA IS NOT THE MAIN
 EGRESS.
 3-SPECIFY SAFETY GLASS WHERE REQUIRED BY
 SEC 2405.2 SBC/97. NEW EGRESS WINDOW
 4-ARCHITECT TO CLEARLY SPECIFY ON DWGS
 THAT GLASS BLOCK @ ZERO LOT LINE NEEDS
 TO BE ONE HOUR FIRE RATED. TABLE 600.
 5-ARCHITECT TO UPDATE SHEET C-1. SEE
 COMMENTS.
 6-REVISE STORM PANEL INSTALLATION SCHED:
 A)SEE MASONRY OPENINGS SPECIFIED BY THE
 ARCHITECT AND REVISE ACCORDINGLY.
 B)INSTALLATION SCHEDULE ANCHOR SPACING
 DOESN'T MATCH THE SPACING SCHEDULE AS
 SHOWN ON SHEETS 5 & 6 OF APPROVED DWGS
 C)CLEARLY WRITE THE ANCHOR SPACING
 ACCORDING TO THE TYPE OF STRUCTURE TO
 BE ATTACHED TO: CONC. OR CONC. BLOCK.
 7-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS (DRAWINGS NOT LEGIBLE).
 B)ARCHITECT TO REVISE DWGS IF TRANSOM
 ABOVE CABANA DOOR IS DELETED. PROVIDE
 PRODUCT APPROVAL FOR DOOR ONLY.
 C)SLIDING GLASS DOORS W/ TRANSOM ABOVE
 SINGLE ASSEMBLY. MULLION PRODUCT
 APPROVAL IS FOR WINDOWS ONLY.
 D)MISSING DWGS FOR 16'-0" GARAGE DOOR.
 E)DRAWINGS FOR GLASS BLOCK PRODUCT
 APPROVAL ARE NOT LEGIBLE.
 -PROVIDE DETAILS AND SPECS FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY.
 F)FIXED WINDOWS WITH SIZES AS SHOWN ON
 ARCHITECT'S EXTERIOR ELEVATIONS.
 G)BUTT GLAZING AND FIXED WINDOW BY
 BREAKFAST AREA.
 -NOTE: SITE SPECIFIC ENGINEERING USE
 CITY SAMPLE FORM, ATTACHED, AND NEEDS
 TO BE SIGNED, SEALED BY THE MANUFACT'R
 ENGINEER AND BY THE PROFESSIONAL OF
 RECORD (REMAINDER: INCLUDE ALL THE
 INFORMATION REQUIRED BY CHAPTER 471 &
 481 OF FLORIDA STATUTES WHEN
 PROFESSIONALS ARE SUBMITTING INFO. FOR
 PUBLIC RECORDS).
 H)PGT ENGINEER, ROBERT L. CLARK PE, TO
 SIGN, SEAL AND DATE LETTER AS REQUIRED
 BY CHAPTER 471 OF FLORIDA STATUTES.
 8-PROVIDE DETAIL AND SPECIFICATIONS FOR
 2X STRUCTURAL BUCK AS REQUIRED FOR
 EXTERIOR DOORS. SEE PRODUCT APPROVAL.
  
  
  
 NOTE:
 PLEASE RETURN REVIEWED SET OF DRAWINGS
 AFTER CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE REVIEW
 PROCESS. THIS WAS NOT DONE FOR THIS SUB-
 MITTAL, THEREFORE, I HAD TO RE-REVIEW
 THE ALL SET AGAIN.