| 2001-06-27 00:00:00 | SECOND CHECKLIST: |
| | 1-MISSING ORIGINAL PERMIT APPLICATION. |
| | 2-ENTRY DOOR TO HAVE 32" MIN. CLEAR |
| | OPENING. TABLE 1004 SBC 1997. |
| | REAR DOOR BY CABANA IS NOT THE MAIN |
| | EGRESS. |
| | 3-SPECIFY SAFETY GLASS WHERE REQUIRED BY |
| | SEC 2405.2 SBC/97. NEW EGRESS WINDOW |
| | 4-ARCHITECT TO CLEARLY SPECIFY ON DWGS |
| | THAT GLASS BLOCK @ ZERO LOT LINE NEEDS |
| | TO BE ONE HOUR FIRE RATED. TABLE 600. |
| | 5-ARCHITECT TO UPDATE SHEET C-1. SEE |
| | COMMENTS. |
| | 6-REVISE STORM PANEL INSTALLATION SCHED: |
| | A)SEE MASONRY OPENINGS SPECIFIED BY THE |
| | ARCHITECT AND REVISE ACCORDINGLY. |
| | B)INSTALLATION SCHEDULE ANCHOR SPACING |
| | DOESN'T MATCH THE SPACING SCHEDULE AS |
| | SHOWN ON SHEETS 5 & 6 OF APPROVED DWGS |
| | C)CLEARLY WRITE THE ANCHOR SPACING |
| | ACCORDING TO THE TYPE OF STRUCTURE TO |
| | BE ATTACHED TO: CONC. OR CONC. BLOCK. |
| | 7-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ENTRY DOORS (DRAWINGS NOT LEGIBLE). |
| | B)ARCHITECT TO REVISE DWGS IF TRANSOM |
| | ABOVE CABANA DOOR IS DELETED. PROVIDE |
| | PRODUCT APPROVAL FOR DOOR ONLY. |
| | C)SLIDING GLASS DOORS W/ TRANSOM ABOVE |
| | SINGLE ASSEMBLY. MULLION PRODUCT |
| | APPROVAL IS FOR WINDOWS ONLY. |
| | D)MISSING DWGS FOR 16'-0" GARAGE DOOR. |
| | E)DRAWINGS FOR GLASS BLOCK PRODUCT |
| | APPROVAL ARE NOT LEGIBLE. |
| | -PROVIDE DETAILS AND SPECS FOR ONE HR |
| | FIRE RATED GLASS BLOCK ASSEMBLY. |
| | F)FIXED WINDOWS WITH SIZES AS SHOWN ON |
| | ARCHITECT'S EXTERIOR ELEVATIONS. |
| | G)BUTT GLAZING AND FIXED WINDOW BY |
| | BREAKFAST AREA. |
| | -NOTE: SITE SPECIFIC ENGINEERING USE |
| | CITY SAMPLE FORM, ATTACHED, AND NEEDS |
| | TO BE SIGNED, SEALED BY THE MANUFACT'R |
| | ENGINEER AND BY THE PROFESSIONAL OF |
| | RECORD (REMAINDER: INCLUDE ALL THE |
| | INFORMATION REQUIRED BY CHAPTER 471 & |
| | 481 OF FLORIDA STATUTES WHEN |
| | PROFESSIONALS ARE SUBMITTING INFO. FOR |
| | PUBLIC RECORDS). |
| | H)PGT ENGINEER, ROBERT L. CLARK PE, TO |
| | SIGN, SEAL AND DATE LETTER AS REQUIRED |
| | BY CHAPTER 471 OF FLORIDA STATUTES. |
| | 8-PROVIDE DETAIL AND SPECIFICATIONS FOR |
| | 2X STRUCTURAL BUCK AS REQUIRED FOR |
| | EXTERIOR DOORS. SEE PRODUCT APPROVAL. |
| | |
| | |
| | |
| | NOTE: |
| | PLEASE RETURN REVIEWED SET OF DRAWINGS |
| | AFTER CORRECTIONS ARE DONE TO ORIGINAL |
| | DRAWINGS IN ORDER TO EXPEDITE THE REVIEW |
| | PROCESS. THIS WAS NOT DONE FOR THIS SUB- |
| | MITTAL, THEREFORE, I HAD TO RE-REVIEW |
| | THE ALL SET AGAIN. |