Plan Review Notes
Plan Review Notes For Permit 01040436
Permit Number 01040436
Review Stop R
Sequence Number 1
Notes
Date Text
2001-05-04 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 2-NEED NOTICE OF COMMENCEMENT.
 3-ENTRY DOORS TO HAVE 32" MIN. CLEAR
 OPENING PER LEAF. TABLE 1004 SBC 1997.
 4-SPECIFY SAFETY GLASS AS REQUIRED BY
 SEC 2405.2 SBC 1997. SEE PLANS.
 5-MASTER BATH GLASS BLOCK TO BE ONE HOUR
 FIRE RATED. TABLE 600 SBC 1997.
 6-UPDATE SHEET C-1: GENERAL NOTES. SEE
 COMMENTS ON THIS SHEET.
 7-PROVIDE EGRESS WINDOW AT LIBRARY ROOM.
 THIS MAY BE CONSIDERED AS A BEDROOM.
 8-ENERGY CALCULATIONS:
 A)REVISE UNDER ATTIC AREA CALCULATED.
 SEC. 602.1.ABC.1.2 FLORIDA ENERGY
 EFFICIENCY CODE, 1997 EDITION.
 B)COMPLETE ADDRESS ON TOP OF FORM
 C)MISSING CALCULATIONS FOR ADJACENT WALL
 D)OWNER/AGENT TO DATE FORM AT THE BOTTOM
 9-REVISE STORM PANELS INSTALLATION SCHED
 AND KEY PLAN TO MATCH ARCHITECT'S PLAN
 10-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS.
 B)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 C)SLIDING GLASS DOORS WITH TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 D)WINDOW MULLIONS(ONE SUBMITTED EXPIRED)
 E)GARAGE DOORS. 8' AND 16'. DADE COUNTY
 OR SBCCI NOT BROWARD COUNTY.
 F)ONE HOUR FIRE RATED GLASS BLOCK.
 G)FIXED WINDOWS AS SHOWN ON ARCHITECT'S
 EXTERIOR ELEVATIONS.
 H)ROUND WINDOW.
 11-SEE PLANS FOR ADDITIONAL COMMENTS.
  
 NOTE: PLEASE RETURN REVIEWED SET OF
 DRAWINGS AFTER CORRECTIONS ARE
 DONE TO ORIGINAL DRAWINGS IN ORDER
 TO EXPEDITE THE REVIEW PROCESS.