| 2001-05-04 00:00:00 | CHECKLIST: |
| | 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | 2-NEED NOTICE OF COMMENCEMENT. |
| | 3-ENTRY DOORS TO HAVE 32" MIN. CLEAR |
| | OPENING PER LEAF. TABLE 1004 SBC 1997. |
| | 4-SPECIFY SAFETY GLASS AS REQUIRED BY |
| | SEC 2405.2 SBC 1997. SEE PLANS. |
| | 5-MASTER BATH GLASS BLOCK TO BE ONE HOUR |
| | FIRE RATED. TABLE 600 SBC 1997. |
| | 6-UPDATE SHEET C-1: GENERAL NOTES. SEE |
| | COMMENTS ON THIS SHEET. |
| | 7-PROVIDE EGRESS WINDOW AT LIBRARY ROOM. |
| | THIS MAY BE CONSIDERED AS A BEDROOM. |
| | 8-ENERGY CALCULATIONS: |
| | A)REVISE UNDER ATTIC AREA CALCULATED. |
| | SEC. 602.1.ABC.1.2 FLORIDA ENERGY |
| | EFFICIENCY CODE, 1997 EDITION. |
| | B)COMPLETE ADDRESS ON TOP OF FORM |
| | C)MISSING CALCULATIONS FOR ADJACENT WALL |
| | D)OWNER/AGENT TO DATE FORM AT THE BOTTOM |
| | 9-REVISE STORM PANELS INSTALLATION SCHED |
| | AND KEY PLAN TO MATCH ARCHITECT'S PLAN |
| | 10-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ENTRY DOORS. |
| | B)FRENCH DOORS WITH TRANSOM ABOVE SINGLE |
| | ASSEMBLY AS SHOWN ON PLANS. |
| | C)SLIDING GLASS DOORS WITH TRANSOM ABOVE |
| | SINGLE ASSEMBLY AS SHOWN ON PLANS. |
| | D)WINDOW MULLIONS(ONE SUBMITTED EXPIRED) |
| | E)GARAGE DOORS. 8' AND 16'. DADE COUNTY |
| | OR SBCCI NOT BROWARD COUNTY. |
| | F)ONE HOUR FIRE RATED GLASS BLOCK. |
| | G)FIXED WINDOWS AS SHOWN ON ARCHITECT'S |
| | EXTERIOR ELEVATIONS. |
| | H)ROUND WINDOW. |
| | 11-SEE PLANS FOR ADDITIONAL COMMENTS. |
| | |
| | NOTE: PLEASE RETURN REVIEWED SET OF |
| | DRAWINGS AFTER CORRECTIONS ARE |
| | DONE TO ORIGINAL DRAWINGS IN ORDER |
| | TO EXPEDITE THE REVIEW PROCESS. |