| 2001-04-20 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | | CODE REQUIREMENTS. | | | 2) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE INSTALLATION OF THE FIRE | | | SPRINKLER SYSTEM. | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE INSTALLATION OF THE FIRE ALARM | | | SYSTEM. | | | 4) A KNOX-BOX RAPID ENTRY SYSTEM WILL | | | BE REQUIRED FOR FIRE RESCUE PURPOSES. | | | APPLICATIONS CAN BE OBTAINED FROM FIRE | | | RESCUE, 835-2910. | | | 5) NO EMERGENCY LIGHTING FIXTURES | | | SHOWN. | | | 6) PLANS ARE TO BE SUBMITTED FOR TENANT | | | REMODEL PRIOR TO BEGINNING WORK. | | | 7) DUCT SMOKE DETECTORS ARE REQUIRED IN | | | AIR HANDLING SYSTEMS OVER 2000 CFM. WHEN | | | ACTIVATED, THEY ARE TO SHUT DOWN AIR | | | HANDLING EQUIPMENT AND ACTIVATE THE | | | BUILDINGS FIRE ALARM SYSTEM. | | | 8) DURING CONSTRUCTION, FIRE HYDRANTS | | | AND SUITABLE ROADS TO ACCESS THE | | | PROPERTY ARE TO BE PROVIDED DURING | | | CONSTRUCTION. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|