| Plan Review Notes For Permit 01040428 |
| Permit Number |
01040428 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-30 00:00:00 | 1 THE BUILDING EXCEEDS THE ARE ALLOWED | | | BY TABLE 600 FOR GROUP B OR S FOR TYPE | | | IV FS CONSTRUCTION.PLEASE REVISE AS | | | NECESSARY. | | | | | | 2IMPACT FEES MUST BE PAID TO THE | | | CONUTY.CALL 233-5025 FOR MORE | | | INFORMATION. | | | | | | 2BLDG WILL BE IN AN A9 FLOOD ZONE BFE | | | 13.0' NGVD>PROVIDE ELEVATION | | | CERTIFICATE. | | | | | | A RESIDENT INSPECTOR IS REQUIRED FOR | | | HTHIS WQORK.CALL DON NEELY 659-8096 X | | | 8333 FOR MORE INFORMATION. | | | | | | PROVIDE PRODUCT APPROVALS FOR THE DOORS, | | | WINDOWS AND ROFF COVERING.SBC 104.2. | | | | | | PLEASE PROVIDE A RECENT SURVEY. | | | | | | SHOW HOW HURRICANE MISSILE IMPACT WILL | | | BE ADDRESSED. | | | | | | SECTION 5/A5.1 IS NOT FOUND ON THE | | | PLANS. | | | SHEET A5.1 SHOWS COMBUSTIBLE TRIM | | | PROJECTING ABOVE THE WALL WHICH IS NOT | | | ALLOWED | | | BY SBC 1401.1.1. |
|