Plan Review Notes
Plan Review Notes For Permit 01040422
Permit Number 01040422
Review Stop M
Sequence Number 1
Notes
Date Text
2001-04-10 00:00:00******************PROVISO***************
  
 AS PER 1997 SMC 406.1, FAN SHUTDOWN BY
 DUCT SMOKE DETECTOR IN THE RETURN AIR
 STREAM PRIOR TO ANY EXHAUSTING FROM THE
 BUILDING OR MIXING WITH FRESH AIR
 MAKEUP, WITH NOTIFICATION TO
 ALARM/STROBE AS PER NFPA 4-4.4.3.