| 2001-04-24 00:00:00 | *******************DENIED*************** |
| | |
| | PLEASE PROVIDE FOLLOWING INFORMATION |
| | WITH MECHANICAL PERMIT APPLICATION. |
| | |
| | 1.SIGN SHALL BE POSTED ON MACHINERY |
| | ROOM DOOR PROHIBITING ACCESS OF |
| | UNAUTHORIZED PERSONNEL. |
| | |
| | 2.EXHAUST OUTLETS SHALL BE LOCATED |
| | 10 FT FROM ANY DOOR, WINDOW OR AIR |
| | INTAKE AND AT LEAST 10 FT ABOVE THE |
| | ADJOINING GRADE LEVEL. 1997 SMC |
| | 506.1 - (H1.1B). |
| | |
| | 3.AS PER 1997 SMC 1105.8, AT LEAST |
| | ONE APPROVED SELF-CONTAINED |
| | BREATHING APPARATUS, SUITABLE |
| | FOR THE REGRIGERANT USED, SHALL BE |
| | AVAILABLE TO AUTHORIZED PERSONNEL |
| | AT A LOCATION CONVENIENT TO THE |
| | MACHINERY ROOM. |
| | |
| | 4.DRAWING E2.1B INDICATES ONE |
| | REFRIGERANT LEAK DETECTOR WILL THIS |
| | SUFFICE FOR THREE CHILLERS?ALSO, |
| | IS THIS TIED INTO THE AUDIBLE/ |
| | VISUAL ALARM? |
| | |
| | 5.ARE THERE TO BE ANY ALARMS LOCATED |
| | OUTSIDE THE DOORS OF THE CHILLER |
| | ROOM IN CASE OF A REFRIGERANT LEAK. |
| | |
| | 6.DRAWING H1.2B, (3) 2" CHILLER |
| | REFIEF RISERS TERMINATE 15' ABOVE |
| | ROOF, SHALL ALSO BE NOT LESS THAN |
| | 20' FROM ANY VENTILATION OPENING IN |
| | REFERENCE TO INTAKE LOUVER TO THE |
| | CHILLED WATER PUMP ROOM. |
| | |
| | 7.PLEASE PROVIDE LOCATION OF THE |
| | BOILERS AND ALSO PROVIDE DETAILS |
| | OF PIPING AND VENTILAITON FOR |
| | THE BOILER ROOM. |