| 2001-04-12 00:00:00 | 1) BOLLARDS SHOWN ON PAGE C1 ARE NOT |
| | TO INTERFERE WITH OPERATION OF THE |
| | FIRE HYDRANT. |
| | 2) ANY ROOM CONTAINING FLAMMABLE OR |
| | COMBUSTIBLE LIQUIDS MUST BE SEPARATED |
| | FROM OTHER PARTS BY AT LEAST A TWO |
| | HOUR FIRE SEPARATION. OPENINGS ARE TO |
| | BE PROTECTED BY B LABELED (1 1/2 HOUR) |
| | FIRE DOORS WITH CLOSERS. ADEQUATE |
| | VETILATION IS TO BE PROVIDED. |
| | 3) STAIRS TO COMPLY WITH NEW STAIRS |
| | PER NFPA 101, THE LIFE SAFETY CODE, |
| | 1985 EDITION. |
| | 4) HANDRAILS AND GUARDS TO COMPLY WITH |
| | NFPA 101, THE LIFE SAFETY CODE, 1985 |
| | EDITION. |
| | 5) THE FIRE DEPARTMENT CONNECTION SHOWN |
| | ON PAGE FP1.1B IS TO BE WITHIN 150 FEET |
| | OF A FIRE HYDRANT. THE REMOVAL AND |
| | RE-INSTALLATION OF THE FIRE PUMP SHALL |
| | BE GIVEN THE HIGHEST PRIORITY FOR |
| | COMPLETION. |
| | 6) EMERGENCY LIGHTING REQUIRED IN FIRE |
| | PUMP ROOM. |
| | 7) PLEASE EXPLAIN RATIONALE FOR EXITING |
| | FROM THE SECOND FLOOR. EXIT STAIR # 6 |
| | IS LOCATED IN A STORAGE ROOM AND |
| | TERMINATES IN A STORAGE ROOM. |
| | 8) PROVIDE MORE DETAILS ON EMERGENCY |
| | GENERATOR AND APPURTENANT EQUIPMENT. |
| | 9) PLEASE INDICATE REFRIGERANT PLANNED |
| | FOR USE. PLEASE INDICATE EMERGENCY |
| | WARNING EQUIPMENT, SIGNS, AND SELF |
| | CONTAINED BREATHING APPARATUS USED IN |
| | THE EVENT OF A REFRIGERANT LEAK. |
| | 10) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR THE FIRE ALARM REMODEL. CUT SHEETS, |
| | WIRING DIAGRAM, AND BATTERY CALCULATIONS |
| | ARE REQUIRED. |
| | |