Plan Review Notes
Plan Review Notes For Permit 01040372
Permit Number 01040372
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-17 00:00:00****************** UNSAT *************
  
 1)NOTE: NOT ENOUGH INFORMATION SUBMITTED
 FOR AN ELECTRICAL REVIEW.
 PLAN ONLY SHOW A REFLECTED CEILING
 LAYOUT.
 PLEASE SUBMIT MORE INFORMATION IF
 ELECTRICAL WORK IS BEING DONE. PLEASE
 NOTE THAT BRANCH CIRCUIT #`S NEED TO BE
 ON PLANS FOR ALL REQ`D OUTLETS PER NEC
 AND LOCAL CODE. ALSO FOR ALL LIGHTING
 AND HOW THEY ARE CONTROLLED. PLEASE
 SUBMIT PANEL
 SCHEDULE(S) THAT CORRELATE WITH BRANCH
 CIRCUIT #`S.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372