| 2001-04-17 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: NOT ENOUGH INFORMATION SUBMITTED | | | FOR AN ELECTRICAL REVIEW. | | | PLAN ONLY SHOW A REFLECTED CEILING | | | LAYOUT. | | | PLEASE SUBMIT MORE INFORMATION IF | | | ELECTRICAL WORK IS BEING DONE. PLEASE | | | NOTE THAT BRANCH CIRCUIT #`S NEED TO BE | | | ON PLANS FOR ALL REQ`D OUTLETS PER NEC | | | AND LOCAL CODE. ALSO FOR ALL LIGHTING | | | AND HOW THEY ARE CONTROLLED. PLEASE | | | SUBMIT PANEL | | | SCHEDULE(S) THAT CORRELATE WITH BRANCH | | | CIRCUIT #`S. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|