Plan Review Notes
Plan Review Notes For Permit 01040371
Permit Number 01040371
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-17 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT NO BRANCH
 CIRCUIT #`S ARE SHOWN ON PLANS FOR
 LIGHTING AND NO SUBMITTED PANEL
 SCHEDULE TO CORRELATE #`S.
 ALSO PLEASE NOTE THAT OUTLETS ARE REQ`D
 BY NEC AND LOCAL CODE PER PALM BEACH
 COUNTY AND CITYWIDE AMENDMENTS FOR
 OFFICES 210-50. PLEASE NOTE THAT FIXED
 GLASS PANELS ARE CONSIDERED WALL SPACE
 BY NEC ART:210-52
  
  
 PLEASE SUBMIT MORE ELECTRICAL DEATIL
 FORREVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELETRICAL PLAN REVIEW
 561-659-8096 EXT 8372