| 2001-04-25 00:00:00 | PLUMBING PLAN REVIEW. | | | | | | DENIED | | | | | | REFERENCE SPC-94 | | | | | | (1) RISER DIAGRAM DOES NOT MEET CODE. | | | | | | (2) 4" TO EXISTING WATER CLOSET. | | | ONLY 2 WATER CLOSETS ON 3" PIPE. | | | | | | (3) VENT MUST BE BETWEEN NEW WATER | | | CLOSETS. | | | | | | (4) SHOWER CAN NOT TIE INTO BASE OF | | | STACK BELOW WASHING MACHINE. | | | | | | (5) SUBMIT SANITARY RISER DIAGRAM WITH | | | PLUMBING PERMIT APPLICATION. | | | | | | REVIEW KEN STEVENS (561) 659-8096 | | | X'S 8389/8377 |
|