2001-04-25 00:00:00PLUMBING PLAN REVIEW.
  
 DENIED
  
 REFERENCE SPC-94
  
 (1) RISER DIAGRAM DOES NOT MEET CODE.
  
 (2) 4" TO EXISTING WATER CLOSET.
 ONLY 2 WATER CLOSETS ON 3" PIPE.
  
 (3) VENT MUST BE BETWEEN NEW WATER
 CLOSETS.
  
 (4) SHOWER CAN NOT TIE INTO BASE OF
 STACK BELOW WASHING MACHINE.
  
 (5) SUBMIT SANITARY RISER DIAGRAM WITH
 PLUMBING PERMIT APPLICATION.
  
 REVIEW KEN STEVENS (561) 659-8096
 X'S 8389/8377