Plan Review Notes
Plan Review Notes For Permit 01040330
Permit Number 01040330
Review Stop B
Sequence Number 1
Notes
Date Text
2001-04-19 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01040330
 O/B JARVIS, JOHN
 213 SEVILLE
  
 1)- ADMINISTRATIVE CODE 104.2.1.-
 ALL INFORMATION, DRAWINGS, SPECIFICATION
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME & SIGNATURE OF THE PERSON RESPON-
 SIBLE FOR THE DESIGN.
  
 2)- SSTD 10-97 101.1 THIS STRUCTURE IS
 TO COMPLY WITH THE REQUIREMENTS FOR
 WIND IN SBC CHAP. 16. THE PRESCRIPTIVE
 METHOD IS TO BE USED. SHOW COMPLIANCE
 WITH EYEBROW AND WINDOW REPAIR.
  
 3)- GLAZED OPENINGS REQUIRE TESTING FOR
 WIND, 1707.4 10 SEC LOAD EQUAL TO 1.5
 THE DESIGN PRESSURE, DADE COUNTY OR
 SBCCI REPORT ACCEPTTED.DOORS & WINDOWS.
  
 4)- DETAIL FRONT STAIRS, THE PLAN INDI-
 CATES THE STRUCTURE TO BE WOOD FRAME,
 SHOW THE AIR GAP BETWEEN THE CONCRETE
 STOOP AND WALL LINE. SBC103.7STATE MEMO
 #692.
  
 5)- SBC 1503.4.1.2. ROOFING SYSTEMS ARE
 TO PROVIDE PRODUCT TESTING FOR 110MPH
 WIND ZONE, SBCCI REPORT OR DADE COUNTY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412