| Plan Review Notes For Permit 01040278 |
| Permit Number |
01040278 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-12 00:00:00 | 1) HOOD, DUCT AND EXTINGUISHING SYSTEM | | | TO COMPLY WITH NFPA 96 AND NFPA 17A. | | | 2) THE DUCT IS TO BE INSPECTED PRIOR | | | TO DUCT WRAP APPLICATION. THE DUCT WHEN | | | WRAPPED IS TO BE INSPECTED. THE WHOLE | | | ASSEMBLY IS THEN TO BE INSPECTED AT THE | | | SITE PRIOR TO LOWERING IT INTO THE TWO | | | HOUR RATED SHAFT. | | | 3) EXHAUST DUCT TO BE A MINIMUM OF TEN | | | FEET FROM AIR INTAKES. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE FIRE SUPPRESSION SYSTEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|