Plan Review Notes
Plan Review Notes For Permit 01040267
Permit Number 01040267
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-09 00:00:00**************** UNSAT *****************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW EQUIPMENT BEING INSTALLED. PER 110-9
 AND 215-5.
  
 2)NOTE: PLEASE NOTE THAT GROUNDING
 ELECTRODETO COLD WATER PIPE ALSO/
 PER 250-50SIZE CONDUCTOR PER 250-66.
  
 3)NOTE: PLEASE NOTE THAT NO PLAN WAS
 SUBMITTED FOR FLOOR PLAN OF HOUSE AND
 LAYOUT FOR ELECTRICAL. PLEASE SUBMIT
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  