| Plan Review Notes For Permit 01040267 |
| Permit Number |
01040267 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-09 00:00:00 | **************** UNSAT ***************** | | | | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | | NEW EQUIPMENT BEING INSTALLED. PER 110-9 | | | AND 215-5. | | | | | | 2)NOTE: PLEASE NOTE THAT GROUNDING | | | ELECTRODETO COLD WATER PIPE ALSO/ | | | PER 250-50SIZE CONDUCTOR PER 250-66. | | | | | | 3)NOTE: PLEASE NOTE THAT NO PLAN WAS | | | SUBMITTED FOR FLOOR PLAN OF HOUSE AND | | | LAYOUT FOR ELECTRICAL. PLEASE SUBMIT | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|