Plan Review Notes
Plan Review Notes For Permit 01040211
Permit Number 01040211
Review Stop P
Sequence Number 1
Notes
Date Text
2001-04-18 00:00:00PLUMBING PLAN REVIEW.
 DENIED:
 SPC 1994 & FACBC 1997
  
 (1)PAGE P-1 WATER HEATER DETAIL,
 PAN DRAIN TO BE 1".
  
 (2)PAGE P-1 WATER HEATER DETAIL,
 RELIEF AND PAN TO DRAIN
 INTO FLOOR SINK NOT
 FLOOR DRAIN.
  
 (3)PAGE P-1 RELIEF TO DISCHARGE TO
 AN OBSERVABLE LOCATION.
  
 (4)PAGE P-1 NOTE # 12 - AIR CHAMBERS
 TO BE ACCESSABLE AND
 RECHARGABLE PER SPC 1994
 607.8.2 & 607.8.3
  
 (5)PAGE P-1 PLUMBING FIXTURE SCHED.
 SINKS TO COMPLY WITH
 FACBC 1997 4.24.2/4.24.3
  
 QUESTION CALL KEN STEVENS
 (561) 659-8096 X'S 8389/8377