2001-04-16 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01040211
 222 LAKEVIEW / 4TH FL
 CATALUMO CONST
 (561) 694-3000 EX 256
  
 1)- SBC 104.2.2. ADDITIONAL INFO:TYPE OF
 BUILDING, TYPE I CONSTRUCTION.
  
 2)- SHEET A-1, A-2 BUCK DETAILS, SBC
 609.2.1. SUB BUCKS TO BE OF FIRE TREATED
 RESISTANT WOOD.
  
 3)- SBC TABLE803.3 MINIMUM INTERIOR
 FINISH CLASSIFICATION NOT GIVEN.
  
 4)- SBC FIRE SPRINKLERS 903.1 A LAYOUT
 OF THE FIRE SPRINKLER PLAN AND EQUIPMENT
  
 5)- SBC 905.1 MANUAL FIRE ALARM SYSTEM:
 GROUP B REQUIRED FOR 100 PERSONS ABOVE
 THE STREET FLOOR.
  
 6)- SBC 104.2.2. ADITIONAL INFORMATION
 DOOR # 1 FIRE RATED ROLL DOWN DOOR,ADD
 INFORMATION REQUIRED.
  
 7)- ROOM # 145 THE EXISTING DOOR DOESN'T
 MEET THE FL ACCESSIBILITY MANEUVERING
 CLEARENCES, FL ACC 4.13.6.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412