| 2001-04-16 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT# 01040211 | | | 222 LAKEVIEW / 4TH FL | | | CATALUMO CONST | | | (561) 694-3000 EX 256 | | | | | | 1)- SBC 104.2.2. ADDITIONAL INFO:TYPE OF | | | BUILDING, TYPE I CONSTRUCTION. | | | | | | 2)- SHEET A-1, A-2 BUCK DETAILS, SBC | | | 609.2.1. SUB BUCKS TO BE OF FIRE TREATED | | | RESISTANT WOOD. | | | | | | 3)- SBC TABLE803.3 MINIMUM INTERIOR | | | FINISH CLASSIFICATION NOT GIVEN. | | | | | | 4)- SBC FIRE SPRINKLERS 903.1 A LAYOUT | | | OF THE FIRE SPRINKLER PLAN AND EQUIPMENT | | | | | | 5)- SBC 905.1 MANUAL FIRE ALARM SYSTEM: | | | GROUP B REQUIRED FOR 100 PERSONS ABOVE | | | THE STREET FLOOR. | | | | | | 6)- SBC 104.2.2. ADITIONAL INFORMATION | | | DOOR # 1 FIRE RATED ROLL DOWN DOOR,ADD | | | INFORMATION REQUIRED. | | | | | | 7)- ROOM # 145 THE EXISTING DOOR DOESN'T | | | MEET THE FL ACCESSIBILITY MANEUVERING | | | CLEARENCES, FL ACC 4.13.6. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|