| 2001-04-17 00:00:00 | ******************DENIED**************** | | | | | | ALL EXISTING FIRE DAMPERS MUST BE | | | INDICATED ON THE PLAN. | | | | | | PLEASE PROVIDE INFORMATION ON EXHAUST | | | FAN TO BE INSTALLED. | | | | | | NO COMBUSTIBLES ABOVE THE CEILING IN THE | | | RETURN AIR PLENUM, 1997 SMC 609.1.1. | | | | | | | | | NOTE:PRIOR TO CONNECTING TO ANY | | | EXISTING DUCTWORK, CALL FOR | | | AN INSPECTION. |
|