Plan Review Notes
Plan Review Notes For Permit 01040196
Permit Number 01040196
Review Stop B
Sequence Number 1
Notes
Date Text
2001-04-13 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01040196
 560 VILLAGE BLVD/ 250
 QUEST CONTRACTING
 691-9400
  
 1)- 1997 FL ACCESSIBILITY CODE 4.1.6.2.2
 ALTERATION TO AN AREA CONTAINING A
 PRIMARY FUNCTION: DISPROPORTIONATE COST
 IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO
 THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER:
 A)ACCESSIBLE ENTRY
 B)ACCESSIBLE ROUTE / ALTERED AREAS
 C)AT LEAST ONE ACCESSIBLE FOR EACH SEX
 OR A UNISEX RESTROOM. NEITHER RESTROOM
 1 OR 2 MEETS THE ACCESSIBILITY CODE.
  
 2)- SBC 903.1 AN APPROVED FIRE SPRINKLER
 LAY OUT( SHOP DRAWINGS) REQUIRED.
  
 3)- SBC TABLE 1004 REQUIRES A MINIMUM OF
 44" FOR CORRIDOR & ISLE WIDTH.
  
 4)- SBC 803.3 MISSING IS INFORMATION ON
 TABLE 803.3 FOR THE MINIMUM INTERIOR
 FINISH CLASSIFICATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 8412