| Plan Review Notes For Permit 01040196 |
| Permit Number |
01040196 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01040196 | | | 560 VILLAGE BLVD/ 250 | | | QUEST CONTRACTING | | | 691-9400 | | | | | | 1)- 1997 FL ACCESSIBILITY CODE 4.1.6.2.2 | | | ALTERATION TO AN AREA CONTAINING A | | | PRIMARY FUNCTION: DISPROPORTIONATE COST | | | IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO | | | PROVIDE, PRIORITY SHOULD BE GIVEN TO | | | THOSE ELEMENTS THAT WILL PROVIDE THE | | | GREATEST ACCESS, IN THE FOLLOWING ORDER: | | | A)ACCESSIBLE ENTRY | | | B)ACCESSIBLE ROUTE / ALTERED AREAS | | | C)AT LEAST ONE ACCESSIBLE FOR EACH SEX | | | OR A UNISEX RESTROOM. NEITHER RESTROOM | | | 1 OR 2 MEETS THE ACCESSIBILITY CODE. | | | | | | 2)- SBC 903.1 AN APPROVED FIRE SPRINKLER | | | LAY OUT( SHOP DRAWINGS) REQUIRED. | | | | | | 3)- SBC TABLE 1004 REQUIRES A MINIMUM OF | | | 44" FOR CORRIDOR & ISLE WIDTH. | | | | | | 4)- SBC 803.3 MISSING IS INFORMATION ON | | | TABLE 803.3 FOR THE MINIMUM INTERIOR | | | FINISH CLASSIFICATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 8412 |
|