Plan Review Notes
Plan Review Notes For Permit 01040106
Permit Number 01040106
Review Stop P
Sequence Number 2
Notes
Date Text
2001-05-06 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) DOOR SWING ON WOMENS REST RM,TO
 SWING OUT,SHOW THIS ON ALL REFERNCES.
 FACBC 4.23.2,4.22.2
 (2) SHOW LOCATION OF SHOCK ARRESTORS,
 AIR CHAMBERS DO NOT COMPLY WITH 607.8.3
 (3) SHT A-3 GREASE WASTE TO COMPLY WITH
 SPC 94 SEC 921.4,MAIN TRUNK LINE 4" ALL
 BRANCHES 3", VENTS ON EACH END.
 (4) NO SAFE WASTE,EACH PLBG FIXTURE TO
 BE INDIVUDALY TRAPED.SEC 1001.8.1
 (5)SHT A-3 GAS RISER,PLEASE COMPLY WITH
 GAS PERMIT APPLICATION REQUIRMENTS,SEE
 ATTACHED,ADDRESS NOTES 2,3,5,9.SEC 104.1
 (6) EMERGENCY SOV BELOW CEILING,MANUAL
 SOV TO BE UP STREAM OF EMERGENCY SOV,
 WITH A UNION DOWN STREAM OF EMERGENCY
 SOV. (SHUT OFF VALVE)
 END OF COMMENTSPAUL SCHMITZ