Notes
Date Text
2001-04-17 00:00:00DENIED;
  
 1.BATHROOM DOORS SWING INTO CLEAR FLOOR
 SPACE OF LAVITORYS.
  
 2.3 COMPARTMENT SINK TO DRAIN INDIRECTLY
 TO A FLOOR SINK. SPC 804.1
  
 3.GREASE TRAP SIZE AND LOCATION MUST BE
 APPROVED BY THE UTILITY DEPARTMENT.
 CALL RODNEY COMPO AT 837-4074.
  
 4.APPROVED ENGINEERED MECHANICAL WATER
 HAMMER ARRESTERS SHALL BE SIZED AND
 INSTALLED PER ENGINEER'S REQUIREMENTS.
 607.8.2 AND 607.8.3.
  
 5.FLOOR DRAINS IN RESTROOMS TO HAVE TRAP
 PRIMERS. 409.4.1.1.
  
 6.GAS RISER;
 A.TYPE OF GAS TO BE INSTALLED.
 B.DELIVERY PSI.
 C.APPROVED GAS CODE IS 97 SGC
 TABLE 305.1A
 D.ANSAL VALVE SHALL BE LOCATED NEXT
 TO HOOD BELOW THE CEILING.
 E.SHUTOFF VALVE SHALL BE INSTALLED
 UP STREAM OF THE EMERGENCY SHUT-
 OFF VALVE.
 F.UNDER SLAB GAS PIPING NOT
 PERMITTED. CHANMEL OUT CONCRETE
 FLOOR COAT GAS PIPE AND FILL
 FLOOR WITH LIGHT WEIGHT CONCRETE.
 G.SIZE ALL PIPE ON GAS RISER.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377