| Plan Review Notes For Permit 01040106 |
| Permit Number |
01040106 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-17 00:00:00 | DENIED; | | | | | | 1.BATHROOM DOORS SWING INTO CLEAR FLOOR | | | SPACE OF LAVITORYS. | | | | | | 2.3 COMPARTMENT SINK TO DRAIN INDIRECTLY | | | TO A FLOOR SINK. SPC 804.1 | | | | | | 3.GREASE TRAP SIZE AND LOCATION MUST BE | | | APPROVED BY THE UTILITY DEPARTMENT. | | | CALL RODNEY COMPO AT 837-4074. | | | | | | 4.APPROVED ENGINEERED MECHANICAL WATER | | | HAMMER ARRESTERS SHALL BE SIZED AND | | | INSTALLED PER ENGINEER'S REQUIREMENTS. | | | 607.8.2 AND 607.8.3. | | | | | | 5.FLOOR DRAINS IN RESTROOMS TO HAVE TRAP | | | PRIMERS. 409.4.1.1. | | | | | | 6.GAS RISER; | | | A.TYPE OF GAS TO BE INSTALLED. | | | B.DELIVERY PSI. | | | C.APPROVED GAS CODE IS 97 SGC | | | TABLE 305.1A | | | D.ANSAL VALVE SHALL BE LOCATED NEXT | | | TO HOOD BELOW THE CEILING. | | | E.SHUTOFF VALVE SHALL BE INSTALLED | | | UP STREAM OF THE EMERGENCY SHUT- | | | OFF VALVE. | | | F.UNDER SLAB GAS PIPING NOT | | | PERMITTED. CHANMEL OUT CONCRETE | | | FLOOR COAT GAS PIPE AND FILL | | | FLOOR WITH LIGHT WEIGHT CONCRETE. | | | G.SIZE ALL PIPE ON GAS RISER. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|