| 2001-04-03 00:00:00 | 1) DUCT SMOKE DETECTORS ARE REQUIRED TO | | | BE CONNECTED TO FIRE ALARM SYSTEM. WHEN | | | ACTIVATED, THEY ARE TO ACTIVATE THE | | | FIRE ALARM SYSTEM AND CAUSE THE AIR | | | HANDLING UNITS TO SHUT DOWN. | | | 2) SMOKE DETECTORS TO BE INSTALLED A | | | MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 3) FIRE ALARM AND FIRE SPRINKLER SYSTEM | | | TO BE SUPERVISED BY A LICENSED UL LISTED | | | CENTRAL STATION APPROVED BY THE FIRE | | | RESCUE DEPARTMENT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|