| Plan Review Notes For Permit 01040043 |
| Permit Number |
01040043 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-03 00:00:00 | 1) PLEASE INDICATE WHAT THE TAPED | | | MESSAGE OF THE VOICE EVACUATION | | | SYSTEM WILL SAY. WHAT INSTRUCTIONS | | | WILL BE GIVEN. | | | 2) SMOKE DETECTORS TO BE INSTALLED A | | | MINIMUM OF THREE FROM AIR CONDITIONER | | | DIFFUSERS. | | | 3) PLEASE INDICATE ON PLANS WHEN SMOKE | | | EXHAUST FANS ARE TO ACTIVATE IN THE | | | STAIRWELLS. DO THEY ACTIVATE ON ANY | | | FIRE ALARM SIGNAL. | | | 4) PLEASE INDICATE ON PLANS THAT HEAT | | | DETECTORS ASSOCIATED WITH ELEVATORS | | | WILL NOT BE CONNECTED TO THE FIRE ALARM | | | SYSTEM AND THAT THEY WILL ONLY SHUNT | | | TRIP ELECTRIC AND OTHER ASSOCIATED | | | DETAILS. | | | 5) FIRE ALARM LEGEND DOES NOT INDICATE | | | WHAT THE DIAMONDS CONTAINING S | | | REPRESENTS. | | | 6) FIRE ALARM SYSTEM TO BE MONITORED BY | | | A UL LISTED CENTRAL STATION APPROVED BY | | | THE FIRE RESCUE DEPARTMENT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|