| 2001-05-10 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE:PLEASE NOTE THAT RESUBMITTAL |
| | SHEET SAYS THAT YOUR ELECTRICAL HAS |
| | CALLED ME AND SPOKEN WITH ME.?? |
| | I DON'T RECALL SPEAKING TO ANYONE ABOUT |
| | THIS PLAN? |
| | |
| | 2)NOTE: ALSO PLEASE NOTE THAT THE NOTE |
| | THAT I GAVE OUTFRONTFOR REVIEW OF |
| | ELECTRICAL IS STILL NOT DRAWN UP ON |
| | PLAN CORRECTLY.PLEASE SEE THE FOLLOWING |
| | NOTES. |
| | |
| | |
| | 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM |
| | SHOWING THE RISER FROM EXISTING TO NEW |
| | SERVICE BEING INSTALLED ON THE COTTAGE. |
| | |
| | PLEASE INCLUDE AIC RATINGS FOR ANY NEW |
| | EQUIPMENT BEING INSTALLED.110-9/215-5 |
| | PLEASE SHOW ALL CONDUIT AND WIRE SIZES. |
| | PLEASE SHOW GROUNDING FROM MAIN HOUSE |
| | TOCOTTAGE AND GROUNDING AT COTTAGE. |
| | 250-24AND 250-32 |
| | PLEASE SUBMIT LOAD CALCUALTIONS FOR NEW |
| | LOADS BEING ADDED TO EXISTING LOAD. |
| | PLEASE SHOW COMBINED TOTAL LOAD. ART |
| | 220AND 215-5. |
| | PLEASE INDICATE PANEL AT DETACHED |
| | STRUCTURE AS MCB. |
| | |
| | 4)NOTE: PLEASE NOTE THAT THE PLAN SHOWS |
| | A TANKLESS WATER HEATER SYSTEM AND LOAD |
| | AT 4800W. PLEASE VERIFY THIS LOAD. |
| | AS MOST HAVE A HIGHER KW RATING. |
| | |
| | 5)NOTE: PLEASE HAVE PLANS REPRINTED |
| | TO CLEAR UP ALL HAND WRITTEN ITEMS ON |
| | PLANS PER COUNTYWIDE AND CITY-WIDE |
| | ADMINISTRATIVE CODE. 104.2/ 104.2.7 |
| | |
| | PLEASE SUBMIT ALL OF THE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |