Plan Review Notes For Permit 01040038
Permit Number 01040038
Review Stop E
Sequence Number 2
Notes
Date Text
2001-05-10 00:00:00***************** UNSAT ***************
  
 1)NOTE:PLEASE NOTE THAT RESUBMITTAL
 SHEET SAYS THAT YOUR ELECTRICAL HAS
 CALLED ME AND SPOKEN WITH ME.??
 I DON'T RECALL SPEAKING TO ANYONE ABOUT
 THIS PLAN?
  
 2)NOTE: ALSO PLEASE NOTE THAT THE NOTE
 THAT I GAVE OUTFRONTFOR REVIEW OF
 ELECTRICAL IS STILL NOT DRAWN UP ON
 PLAN CORRECTLY.PLEASE SEE THE FOLLOWING
 NOTES.
  
  
 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM
 SHOWING THE RISER FROM EXISTING TO NEW
 SERVICE BEING INSTALLED ON THE COTTAGE.
  
 PLEASE INCLUDE AIC RATINGS FOR ANY NEW
 EQUIPMENT BEING INSTALLED.110-9/215-5
 PLEASE SHOW ALL CONDUIT AND WIRE SIZES.
 PLEASE SHOW GROUNDING FROM MAIN HOUSE
 TOCOTTAGE AND GROUNDING AT COTTAGE.
 250-24AND 250-32
 PLEASE SUBMIT LOAD CALCUALTIONS FOR NEW
 LOADS BEING ADDED TO EXISTING LOAD.
 PLEASE SHOW COMBINED TOTAL LOAD. ART
 220AND 215-5.
 PLEASE INDICATE PANEL AT DETACHED
 STRUCTURE AS MCB.
  
 4)NOTE: PLEASE NOTE THAT THE PLAN SHOWS
 A TANKLESS WATER HEATER SYSTEM AND LOAD
 AT 4800W. PLEASE VERIFY THIS LOAD.
 AS MOST HAVE A HIGHER KW RATING.
  
 5)NOTE: PLEASE HAVE PLANS REPRINTED
 TO CLEAR UP ALL HAND WRITTEN ITEMS ON
 PLANS PER COUNTYWIDE AND CITY-WIDE
 ADMINISTRATIVE CODE. 104.2/ 104.2.7
  
 PLEASE SUBMIT ALL OF THE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372