Plan Review Notes
Plan Review Notes For Permit 01031347
Permit Number 01031347
Review Stop P
Sequence Number 2
Notes
Date Text
2001-05-06 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) SHT.A1 WOMENS REST RM, COMPLY WITH
 FACBC 4.17.3 H/C W/C,LAV IN A STALL.
 (2) SHT A2 GAS WATER HEATER, CALCULATION
 FOR COMBUSTION AIR SGC 97 SEC 402.4
 (3) LETTER FROM WPB REG SEWER PLANT FOR
 GREASE TRAP SIZE, R.COMPO 837- 4074
 (4) S/SEWER PUBLIC REST RM,NOT OVER 2
 W/C ON 3" WASTE LINE.
 (5) AIR CHAMBER DETAIL:DOES NOT COMPLY
 WITH SEC 607.8.3,ACCESSIBLE,RECHARGEABLE
 (6) GREASE WASTE RISER: GREASE WASTE TO
 COMPLY WITH SPC SEC 921.4,MAIN TRUNK 4"
 ALL BRANCHES 3", VENTS ON EACH END.
 (7)GAS PIPING UNDER SLAB DETAIL: TO
 COMPLY WITH SGC 97 SEC 308.4.2(2)
 CHANNEL FLR,LIGHT WEIGHT CONCRETE.
 (8) GAS RISER: PLEASE COMPLY WITH GAS
 PERMIT APPLICATION REQUIRMENTS, SGC 97
 SEC.104.1.2, NOTES 2,3,5,6,7,8,9.
 SEE ATTACHED.
 (9)EMERGENCY SOV BELOW CEILING (ESOV).
 MANUAL SOV TO BE UP STREAM OF ESOV WITH
 A UNION DOWN STREAM OF ESOV.SEC 103.5
 END OF COMMENTSPAUL SCHMITZ