| Plan Review Notes For Permit 01031347 |
| Permit Number |
01031347 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-05-09 00:00:00 | ********************DENIED************** | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION. | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.AIR BALANCE SCHEDULE. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHOULD UNIT HAVE THE CAPACITY | | | GREATER THAN 2,000 CFM. | | | | | | 4.WHEN UNIT CAPACITY IS GREATER THAN | | | 2,000 CFM & FAN SHUTDOWN APPLIES, | | | NOTIFICATION TO ALARM/STROBE AS PER | | | NFPA 4-4.4.3, WILL ALSO APPLY. | | | | | | 5.ADDITIONAL MECHANICAL PERMITS/PLANS | | | FOR ANY HOOD, FIRE SUPPRESSION OR | | | WALK-IN COOLERS. | | | | | | 6.PRIOR TO CONNECTING TO ANY EXISTING | | | DUCTWORK, CALL FOR AN INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|