2001-04-16 00:00:00DENIED;
  
 1.PLANS MUST BE REVIEWED AND APPROVED BY
 THE HOTEL BUISNESS REGULATIONS AT
 954-958-5520.
  
 2.CONTACT THE CITY UTILITY DEPARTMENT.
 RODNEY COMPO AT 837-4074 FOR APPROVAL
 OF GREASE TRAP SIZE AND LOCATION.
  
 3.1997 STANDARD GAS CODE TABLE 305.4A
 SHALL BE USED TO SIZE GAS PIPE.
  
 4.DELETE UNDER SLAB GAS PIPE DETAIL. NO
 GAS PIPE IS SHOWN ON DRAWINGS UNDER
 SLAB.
  
 5.DISHWASHER TO DISHCHARGE INDIRECTLY
 INTO SANITARY FLOOR SINK NOT GREASY
 WASTE. CITY ORD.
  
 6.AIR CHAMBERS SHALL BE ENGINEERED
 MECHANICAL WATER HAMMER ARRESTERS AND
 SIZED BY AN ENGINEER. PER 94 SPC
 607.8.2 AND 607.8.3.
  
 7.GREASE TRAP DETAIL; TWO WAY CLEANOUTS
 REQUIRED.
  
 8.TWO COMPARTMENT SINK SHALL BE
 INDIRECTLY WASTED. 804.1
  
 9.EMERGENCY SHUTOFF VALVE FOR GAS PIPING
 SHALL BE INSTALLED BELOW THE CEILING.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT;8377