| Plan Review Notes For Permit 01031347 |
| Permit Number |
01031347 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-16 00:00:00 | DENIED; | | | | | | 1.PLANS MUST BE REVIEWED AND APPROVED BY | | | THE HOTEL BUISNESS REGULATIONS AT | | | 954-958-5520. | | | | | | 2.CONTACT THE CITY UTILITY DEPARTMENT. | | | RODNEY COMPO AT 837-4074 FOR APPROVAL | | | OF GREASE TRAP SIZE AND LOCATION. | | | | | | 3.1997 STANDARD GAS CODE TABLE 305.4A | | | SHALL BE USED TO SIZE GAS PIPE. | | | | | | 4.DELETE UNDER SLAB GAS PIPE DETAIL. NO | | | GAS PIPE IS SHOWN ON DRAWINGS UNDER | | | SLAB. | | | | | | 5.DISHWASHER TO DISHCHARGE INDIRECTLY | | | INTO SANITARY FLOOR SINK NOT GREASY | | | WASTE. CITY ORD. | | | | | | 6.AIR CHAMBERS SHALL BE ENGINEERED | | | MECHANICAL WATER HAMMER ARRESTERS AND | | | SIZED BY AN ENGINEER. PER 94 SPC | | | 607.8.2 AND 607.8.3. | | | | | | 7.GREASE TRAP DETAIL; TWO WAY CLEANOUTS | | | REQUIRED. | | | | | | 8.TWO COMPARTMENT SINK SHALL BE | | | INDIRECTLY WASTED. 804.1 | | | | | | 9.EMERGENCY SHUTOFF VALVE FOR GAS PIPING | | | SHALL BE INSTALLED BELOW THE CEILING. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT;8377 |
|