| Plan Review Notes For Permit 01031347 |
| Permit Number |
01031347 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01031347 | | | 444 24TH ST | | | L & L INTERIORS | | | 688-2844 | | | | | | 1)- SBC 1019.7.2. EACH DOOR IN A MEANS | | | OF EGRESS FROM AN AREA OF GROUP A OCCU- | | | PANCY MAY BE PROVIDED WITH A LATCH OR | | | LOCK ONLY IF IT IS PANIC HARDWARE OR | | | FIRE EXIT HARDWARE, WHICH RELEASES WHEN | | | NO MORE THAN 15LBS. PRESSURE IS APPLIED | | | TO THE RELEASING DEVICES IN THE DIREC- | | | TION OF THE EXIT TRAVEL. | | | | | | 2)- SBC 803.3 THE MINIMUM INTERIOR | | | FINISH CLASSIFICATION IS NOT INDICATED. | | | | | | 3)- SBC 1204.2 THE WALLS & FLOORS OF ALL | | | PUBLIC RESTROOMS SHALL BE LINED WITH | | | NONABSORBANT MATERIALS TO A HEIGTH OF | | | 4FT. ABOVE THE FLOOR. | | | | | | 4)- FL ACCESSIBILITY CODE 4.1.6 ALTERA- | | | TIONS CONTAINING A PRIMARY FUNCTION AREA | | | AN ACCESSIBILE ENTRENCE IS REQUIRED WITH | | | ONE RAMPED ENTRY. | | | | | | 5)- FL. ACCESIBILITY CODE 5.1 PROVIDE | | | AT LEAST 5% BUT LESS THAN ONE OF THE FIX | | | ED TABLES OR A PORTION OF THE COUNTER | | | SHALL BE ACCESSIBLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412. |
|