2001-04-13 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01031347
 444 24TH ST
 L & L INTERIORS
 688-2844
  
 1)- SBC 1019.7.2. EACH DOOR IN A MEANS
 OF EGRESS FROM AN AREA OF GROUP A OCCU-
 PANCY MAY BE PROVIDED WITH A LATCH OR
 LOCK ONLY IF IT IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE, WHICH RELEASES WHEN
 NO MORE THAN 15LBS. PRESSURE IS APPLIED
 TO THE RELEASING DEVICES IN THE DIREC-
 TION OF THE EXIT TRAVEL.
  
 2)- SBC 803.3 THE MINIMUM INTERIOR
 FINISH CLASSIFICATION IS NOT INDICATED.
  
 3)- SBC 1204.2 THE WALLS & FLOORS OF ALL
 PUBLIC RESTROOMS SHALL BE LINED WITH
 NONABSORBANT MATERIALS TO A HEIGTH OF
 4FT. ABOVE THE FLOOR.
  
 4)- FL ACCESSIBILITY CODE 4.1.6 ALTERA-
 TIONS CONTAINING A PRIMARY FUNCTION AREA
 AN ACCESSIBILE ENTRENCE IS REQUIRED WITH
 ONE RAMPED ENTRY.
  
 5)- FL. ACCESIBILITY CODE 5.1 PROVIDE
 AT LEAST 5% BUT LESS THAN ONE OF THE FIX
 ED TABLES OR A PORTION OF THE COUNTER
 SHALL BE ACCESSIBLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412.