Plan Review Notes
Plan Review Notes For Permit 01031345
Permit Number 01031345
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-04-04 00:00:001) THE ENTIRE BUILDING IS TO BE
 COMPLETELY FIRE SPRINKLER PROTECTED.
 THIS INCLUDES ALL ELECTRICAL, MECHANICAL
 AND SERVICE ROOMS.
 2) PLEASE PROVIDE MORE DETAILS ON FIRE
 PUMP ASSEMBLY. IS THE FIRE PUMP
 ELECTRICAL OR DEISEL. PLEASE PROVIDE
 COMPLETE PLANS ON THE INSTALLATION OF
 THE FIRE PUMP AND APPURTENANT EQUIPMENT.
 3) THE FIRE PUMP INSTALLATION TO
 COMPLY WITH NFPA 20.
 4) THE FIRE SPRINKLER SYSTEM IS TO
 COMPLY WITH NFPA 13.
 5) THE STANDPIPE SYSTEM IS TO COMPLY
 WITH NFPA 14.
 6) PLANS DO NOT INDICATE FIRE HYDRANT
 LOCATIONS OR UNDERGROUND UTILITIES.
 7) PLEASE INDICATE LOCATION OF BACKFLOW
 DEVICE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910