| Plan Review Notes For Permit 01031345 |
| Permit Number |
01031345 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-04 00:00:00 | 1) THE ENTIRE BUILDING IS TO BE | | | COMPLETELY FIRE SPRINKLER PROTECTED. | | | THIS INCLUDES ALL ELECTRICAL, MECHANICAL | | | AND SERVICE ROOMS. | | | 2) PLEASE PROVIDE MORE DETAILS ON FIRE | | | PUMP ASSEMBLY. IS THE FIRE PUMP | | | ELECTRICAL OR DEISEL. PLEASE PROVIDE | | | COMPLETE PLANS ON THE INSTALLATION OF | | | THE FIRE PUMP AND APPURTENANT EQUIPMENT. | | | 3) THE FIRE PUMP INSTALLATION TO | | | COMPLY WITH NFPA 20. | | | 4) THE FIRE SPRINKLER SYSTEM IS TO | | | COMPLY WITH NFPA 13. | | | 5) THE STANDPIPE SYSTEM IS TO COMPLY | | | WITH NFPA 14. | | | 6) PLANS DO NOT INDICATE FIRE HYDRANT | | | LOCATIONS OR UNDERGROUND UTILITIES. | | | 7) PLEASE INDICATE LOCATION OF BACKFLOW | | | DEVICE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|