Plan Review Notes
Plan Review Notes For Permit 01031312
Permit Number 01031312
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-04 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOT ENOUGH
 INFORMATION WAS SUBMITTED FOR REVIEW.
 PLEASE SUBMIT INFORMATION FOR WHERE
 ELECTRICAL IS COMING FROM??????
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 MISSING SD IN CABANNA.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  