2001-04-02 00:00:00************** PROVISO ***************
  
 1)NOTE: PLEASE CLARIFY GFI PROTECTION
 FOR MAIN SERVICE PER 230-95.
  
 2)NOTE: PLEASE NOTE THAT PLANS ARE
 SHOWING FUTURE ATS AND GENERATOR.
 PLEASE NOTE THAT PER 225-31 A
 DISCONNECT IS REQ`D. 230-72,
 230,76,230-79.THIS A JUST A NOTE BECAUSE
 IT MIGHT END UP CHANGING LAYOUT OF
 ROOM. PLEASE CALL FOR ANY CLARIFICATION.
  
 3)NOTE: PLEASE NOTE GROUNDING ELECTRODE
 TO COLD WATER PIPE PER 250-50.
  
 PLEASE SUBMIT CLARIFICATION ON THE ABOVE
 NOTES. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW