Plan Review Notes
Plan Review Notes For Permit 01031191
Permit Number 01031191
Review Stop P
Sequence Number 1
Notes
Date Text
2001-05-07 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) SHT PL-100 GENERAL NOTES
 CODE REFERENCE STD PLBG CODE 1994
 HAND WRITTEN REFERENCE TO CPVC TO BE
 INCLUDED IN SPECIFICATIONS.
 (2) TWO WAY CO'S REQUIRED ON BLDG SEWER
 WITHIN 3' OF FOUNDATION WALL,SEC 710.4
 (3) SHTS PL-101,PL-901, NO MORE THAN 2
 FIXTURES ON 1/2" COLD WATER.
 NO MORE THAN 4 FIFTURES ON 1/2" HOT
 WATER, CNTY. WIDE AMEDMENTS TO THE 1994
 STD PLUMBING CODE.
 (4) MAXIM NUMBER OF FIXTURES UNITS ON
 BUILDING SEWERS AND BRANCHES,SEC 714.
 MIN SIZE FOR A WATER CLOSET DRAIN 3".
 NO MORE THAN 2 WATER CLOSETS ON 3"DRAIN.
 END OF COMMENTS. PAUL SCHMITZ
 QUESTIONS561-659-8096