Plan Review Notes
Plan Review Notes For Permit 01031191
Permit Number 01031191
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-04-05 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 2) CODE ANALYSIS BOX INDICATES 1998
 EDITION OF THE LIFE SAFETY CODE. DO
 YOU MEAN 1997 OR 2000 EDITION.
 3) ANY CHANGES IN ELEVATION LESS THAN
 21 INCHES SHALL BE BY RAMPS. STAIRS IF
 PRESENT, SHOULD CONSIST OF THREE AT 7
 INCHES EACH.
 4) PLEASE INDICATE AGES OF CHILDREN AND
 PROPOSED HOURS OF OPERATION.
 5) NEW SHADE AWNING OVER PLAYGROUND IS
 TO BE FIRE RETARDANT IF PERSONS WILL
 BE UNDERNEATH IT.
 6) ON PAGE A001, SECTION K INDICATES
 NO PANIC HARDWARE. ON PAGE AE101, DOOR
 SCHEDULE, PANIC HARDWARE IS NOTED.
 PLEASE CLARIFY.
 7) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS WITH A PERMIT. CUT SHEETS,
 WIRING DIAGRAM AND BATTERY CALCULATIONS
 ARE TO BE PROVIDED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910