| Plan Review Notes For Permit 01031191 |
| Permit Number |
01031191 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-16 00:00:00 | *****************UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS. PLEASE CORRELATE WITH | | | PANEL SCHEDULES THAT NEED TO BE | | | SUBMITTED. | | | | | | 2)NOTE: PLEASE NOTE THAT PER FS | | | 481.0221AND 471.025. ALL CHANGES ON | | | PLANS THAT ARE SIGNED AND SEALED, NEED | | | TO HAVE THOSE CHANGES DONE BY THAT | | | ARCH/ENG OF RECORD | | | | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | AIC RATING SHOWN FOR ONE MIAN DISCONNECT | | | BUT NOT FOR OTHER OR PANELS. | | | | | | 3)NOTE: PLEASE NOTE THAT NO LOAD | | | CALCULATIONS WERE SUBMITTED. 215-5 | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|