Plan Review Notes
Plan Review Notes For Permit 01031191
Permit Number 01031191
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-16 00:00:00*****************UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS. PLEASE CORRELATE WITH
 PANEL SCHEDULES THAT NEED TO BE
 SUBMITTED.
  
 2)NOTE: PLEASE NOTE THAT PER FS
 481.0221AND 471.025. ALL CHANGES ON
 PLANS THAT ARE SIGNED AND SEALED, NEED
 TO HAVE THOSE CHANGES DONE BY THAT
 ARCH/ENG OF RECORD
  
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 AIC RATING SHOWN FOR ONE MIAN DISCONNECT
 BUT NOT FOR OTHER OR PANELS.
  
 3)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED. 215-5
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  