Plan Review Notes
Plan Review Notes For Permit 01031095
Permit Number 01031095
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-03-28 00:00:001) A SEPARATE FIRE ALARM CONTROL PANEL
 INSTALLATION WILL NOT BE ACCEPTED.
 2) DUCT SMOKE DETECTORS WHEN ACTIVATED
 ARE TO SHUT DOWN THE AIR HANDLING
 EQUIPMENT AND CAUSE THE FIRE ALARM
 SYSTEM TO ACTIVATE. ACCORDING TO THE
 NOTES DUCT SMOKE DETECTORS WILL ONLY
 CAUSE A SUPERVISORY SIGNAL.
 3) SMOKE DETECTORS WHEN INSTALLED ARE TO
 BE A MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 4) SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE.
 5) AN AS-BUILT SET OF PLANS ARE TO BE
 SUBMITTED WITHOUT THE FIRE ALARM PANEL
 SHOWN.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910