| 2001-04-13 00:00:00 | CHECKLIST:1ST REVIEW LEA SMITH |
| | 1. STORM PANELS ARE TO BE PERMITTED |
| | SEPARATELY.WILL NEED KEY PLAN OF ALL |
| | OPENINGS TO BE PROTECTED AND PRODUCT |
| | APPROVALS WITH FASTENERS HIGHLIGHTED. |
| | 2. DADE COUNTY PRODUCT APPROVAL FOR THE |
| | WINDOWS IS MISSING.ONLY THE DRAWINGS |
| | WERE SUBMITTED WITH APPLICATION. THE |
| | DRAWINGS WERE NOT MARKED AS TO THE |
| | METHOD OF INSTALLATION OR TYPE OF WINDOW |
| | BEING INSTALLED, NO MULLINS FOR S/H WIND |
| | OWS WAS FOUND. |
| | 3. TRUSS DRAWINGS DO NOT MATCH ARCHITECT |
| | DRAWING 3A AT AREA OF BATH#2.CORRECT |
| | DRAWING THAT IS INCORRECT. |
| | 4. PRODUCT APPROVAL FOR ROOF TILE NOT |
| | MARKED FOR TYPES OF PRODUCTS TO BE USED |
| | PLEASE MARK THE ITEMS TO BE USED FOR THE |
| | TILE ROOF INSTALLATION. |
| | 5. PRODUCT APPROVAL FOR 2 DIFFERENT |
| | FRENCH DOORS (DOUBLE) ONE WITH SIDELITE |
| | WAS SUBMITT. WHERE DO THEYGO? |
| | |
| | 6. SHEET 2 OF 6 SHOWS FRONT DOORS ARE TO |
| | BE PAIR OF 3'0X8'0 SOLID CORE. DID NOT |
| | SEE ANY PRODUCT APPROVALS FOR THESE. |
| | 7. SINGLE 2'8"X8'0"DOOR OFF BREAKFAST |
| | APPEARS TO BE A SINGLE FRENCH DOOR.NO |
| | PRODUCT APPROVAL FOR SINGLE FRENCH DOOR |
| | WAS FOUND IN SUBMITTAL PKG. |
| | 7. PROPERTY LOCATED IN "A" FLOOD ZONE. |
| | ELEVATION CERTIFICATE WHEN REQUIRED MUST |
| | BE SUBMITTED BEFORE CO. |
| | |
| | NOTE: PLEASE RETURN BOTH REVIEWED SETS |
| | WHEN CORRECTIONS HAVE BEEN COMPLETED. |
| | WHEN ALL ITEMS ARE CORRECTED WE CAN |
| | PROCESS YOUR PERMIT.ANY QUESTIONS |
| | PLEASE CALL LEA SMITH, PLAN REVIEW @ |
| | 659-8096 EXT 8394. |