| Date |
Text |
| 2001-06-24 00:00:00 | ****************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT LOAD |
| | CALCUALTIONS THAT ARE SHOWN NEED TO BE |
| | DONE TO |
| | ART 220 OF THE 99 NEC. PLEASE LOAD |
| | CALCULATIONS PER ART 220. |
| | |
| | 2)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| | NEED TO SHOW EXISTING HOUSE SERVICE AS |
| | WELL. IS THERE A MAIN AT EXIST. PANEL? |
| | PLEASE SHOW GROUNDING AT MAIN HOUSE. |
| | YOU SHOW 3-#4`S COMING FROM A 200A |
| | DISC?YOU ARE SHOW #4 WITH 200A`S OF |
| | OCP. |
| | |
| | 3) NOTE: PLEASE SHOW GROUNDING |
| | ELECTRODE GOING TO BUILDING STEEL AND |
| | COLD WATER |
| | PER 250-50. MISSING COLD WATER AT BOTH |
| | STRUCTURES. |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | PLEASE NOTE THAT THESE PLANS THAT ARE |
| | BEING SUBMITTED ARE NOW SHOWING A NEW |
| | SERVICE AND THIS INFORMATION IS REQ`D. |
| | |
| | 5) PLEASE CLARIFY EQUIPMENT GROUNDING |
| | METHOD BETWEEN FIRST MEANS OF |
| | DISCONNECT AND PANEL(S). EQUIPMENT |
| | GROUNDING |
| | CONDUCTORS ARE TO BE SIZED BY 250-122. |
| | |
| | 6) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | THIS WAS ASKED FOR ON FIRST REVIEW. |
| | |
| | 7)NOTE: PLEASE NOTE THAT ONLY ONE PANEL |
| | SCHEDULE WAS SUBMITTED AND LOAD |
| | CALCULATIONS NEED TO BE SHOWN FOR EACH |
| | PANEL. PLANS SHOW 60A FEED FOR MAIN |
| | HOUSE. ARE THERE ALL GAS APPLIANCES? |
| | |
| | 8)NOTE: PLEASE NOTE THAT A/C EQUIPMNET |
| | IS MISSING FROM THE ELECTRICAL PLANS. |
| | NEED TO SHOW DISCONNECTS PER 440-11. |
| | |
| | 9)NOTE: ,PLEASE NOTE THAT LOAD CALCS SHO |
| | W #12 AWG WITH 30A OCP? PLEASE CALRIFY. |
| | PLEASE CLARIFY SPECIAL EFFECT LIGHTING |
| | SHOWN W/ 2P50A AND #8?PLEASE SUBMIT |
| | ANY SPECS ON ANY SPECIAL LIGHTING |
| | EQUIPMENT BEING INSTALLED. PLANS DON'T |
| | SHOW ANY SPEC LIGHTING? |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |