2001-04-09 00:00:00CHECKLIST:
 1-ONE AND TWO FAMILY DWELLINGS MAY NOT
 REQUIRE AN ARCHITECT OR ENGINEER
 PROVIDED THAT ENTIRE DWELLING CONFORMS
 TO A PRESCRIPTIVE STANDARD ADOPTED BY
 THE CITY: SSTD 10-97. THEREFORE,
 DESIGNER SHALL USE THIS BOOK TO
 DESIGN THE STRUCTURE.
 SECTION 104.2.3 OF CITY AMENDMENTS.
 2-DESIGNER TO PROVIDE HIS/HER NAME AND
 SIGNATURE ON ALL DRAWINGS AS REQUIRED
 BY SECTION 104.2.1 OF CITY AMENDMENTS.
 3-BRING DRAWINGS TO PALM BEACH COUNTY TO
 VERIFY IF NEED TO PAY IMPACT FEES.
 BRING COUNTY STAMPED DRAWINGS AND
 RECEIPT AS REQUIRED.
 4-DOOR FROM GARAGE TO BEDROOM IS NOT
 ALLOWED. SECTION 411.2.8 SBC 1997.
 5-CLEARLY SPECIFY WINDOW TYPES AND SIZES
 -SPECIFY DOOR SIZES.
 6-PROVIDE PRODUCT APPROVAL FOR:
 -EXTERIOR DOORS AND WINDOWS.
 -GARAGE DOORS WITH SIZES AS SHOWN ON
 PLANS AND ELEVATIONS.
 -FLAT ROOF SYSTEM TO BE USED.
 7-STORM PANELS:
 -PROVIDE PRODUCT APPROVAL.
 -PROVIDE KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE AS PER CITY
 SAMPLE ATTACHED.
 -CLEARLY INDICATE ON STORM PANEL
 DRAWINGS THE SPECIFIC MOUNTING
 CONDITIONS, ANCHOR TYPE AND SPACING TO
 BE USED ACCORDING TO THE MEAN ROOF
 HEIGHT, DESIGN PRESSURES, PANEL SPAN,
 EDGE DISTANCE, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE
 BLOCK).
 8-PROVIDE COMPLETE STRUCTURAL BUCK
 DETAILS FOR GARAGE DOORS, WINDOWS AND
 EXTERIOR DOORS.
 SECTION 104.2.2 OF CITY AMENDMENTS.
 9-PROVIDE ENERGY CALCS. AS REQUIRED BY
 THE FLORIDA ENERGY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 10-CLEARLY SPECIFY ON PLANS HOW THE
 OPENINGS FOR DOORS AND WINDOWS ARE
 REINFORCED.
 -SPECIFY HOW ARE BUILDING CORNERS
 REINFORCED.
 -PROVIDE BEAM AND LINTEL SCHEDULE.
 -CLARIFY IF ROOF IS GOING TO HAVE
 PARAPET WALLS OR NOT. AND HOW IS THE
 WATER GOING TO RUN OFF.
 11-PROVIDE A COMPLETE HURRICANE ANCHOR
 SCHEDULE FOR ROOF FRAMING. AND SPECIFY
 UPLIFT LOADS AS CALCULATED ACCORDING
 TO THE PRESCRIPTIVE METHOD SSTD 10-97.
 12-SPECIFY TYPE AND GRADE OF STRUCTURAL
 LUMBER TO BE USED.
 13-SPECIFY HOW THE ROOF IS GOING TO BE
 VENTILATED AS REQUIRED BY SECTION
 2309.7 OF SBC 1997.
 14-SPECIFY SAFETY GLASS (TEMPERED GLASS)
 FOR WINDOWS WITHIN 24" RADIOUS OF
 SWING DOORS AS REQUIRED BY SECTION
 2405.2 SBC 1997.
 15-ROOF SHEATHING TO BE 19/32" MIN. NOT
 1/2". ALSO, SPECIFY NAIL TYPE AND
 SPACING AS REQUIRED BY SECTION 2306 OF
 CITY AMENDMENTS TO SBC 1997.
 16-FLAT ROOF TO HAVE A MINIMUM SLOPE OF
 1/4" PER FT. SEC. 1503.1.2.3 SBC 1997.
 17-TOILET ROOM TO HAVE WINDOW WITH MIN.
 3 SQ. FT. OF OPEN AREA OR PROVIDE
 MECHANICAL VENTILATION AS REQUIRED BY
 SECTION 1203.4.2 OF SBC 1997.
 18-FILE NOTICE OF COMENCEMENT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.