| Plan Review Notes For Permit 01030959 |
| Permit Number |
01030959 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-04 00:00:00 | **************** UNSAT *************** | | | | | | 1) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 2)NOTE: PLEASE PROVIDE CLARIFICATION | | | FORPOWER AND WHERE ITS COMING FROM. | | | PLANS | | | SHOW AN 100A PANEL AND NO OTHER DETAIL, | | | | | | 3)NOTE: PLEASE NOTE, PLEASE SHOW ALL | | | OUTLETS FOR GARAGE AS GFI/GFI PROTECTED | | | PER 210-8. | | | | | | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 5)NOTE: PLEASE PROVIDE CLARIFICATION ON | | | GROUNDING/ AT DETACHED STRUCTURE. | | | | | | PLEASE PROVIDE THE ABOVE INFORMATION | | | FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|