Plan Review Notes
Plan Review Notes For Permit 01030959
Permit Number 01030959
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-04 00:00:00**************** UNSAT ***************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 2)NOTE: PLEASE PROVIDE CLARIFICATION
 FORPOWER AND WHERE ITS COMING FROM.
 PLANS
 SHOW AN 100A PANEL AND NO OTHER DETAIL,
  
 3)NOTE: PLEASE NOTE, PLEASE SHOW ALL
 OUTLETS FOR GARAGE AS GFI/GFI PROTECTED
 PER 210-8.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5)NOTE: PLEASE PROVIDE CLARIFICATION ON
 GROUNDING/ AT DETACHED STRUCTURE.
  
 PLEASE PROVIDE THE ABOVE INFORMATION
 FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372