Plan Review Notes
Plan Review Notes For Permit 01030953
Permit Number 01030953
Review Stop B
Sequence Number 2
Notes
Date Text
2001-10-16 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01030953
 204 MONROE DR
 CONT : W L SCHIELE
 TEL: 762-0511
  
 1)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 ALL GLAZED OPENINGS SHALL REQUIRE A
 PRODUCT APPROVAL TESTING REPORT INDICAT-
 ING THAT THE PRODUCT HAS MET THE LARGE
 MISSLE RESISTANCE TESTING.
 IF THEY PRODUCT HASN'T BEEN TESTED THEN
 STORM SHUTTERS SHALL BE REQUIRED THAT
 HAVE MET THIS CRITERIA. THE CITY ACCEPTS
 EITHER SBCCI OR DADE COUNTY PRODUCT
 TESTING REPORTS.
 A)- MISSING REPORT FOR THE FRENCH DOORS
 SINGLE AS WELL AS DOUBLE DOORS.
 B)- MISSINGTEST REPORT FOR MULLIONS
 C)- STORM SHUTTERS WILL BE REQUIRED,
 THE PRODUCT TESTING REPORT IS ONLY
 PART OF THE INFORMATION REQUIRED, A
 KEY PLAN AND FASTENING SCHEDULE FOR
 EACH OPENING, A SAMPLE IS ATTACHED.
 D)- A COPY OF CASEMENT WINDOWS IS STILL
 INCLUDED IN THE PERMIT PACKAGE, IS
 THIS PRODUCT STILL TO BE INSTALLED
 INTO THE ADDITION?
  
 2)- STATE STATUTE 61 G1.001ARCHITECTS
 SHALL IDENITY ALL PLANS, SPECIFICATIONS
 OR REPORTS PREPARED OR ISSUED BY HIM &
 FILED FOR PUBLIC RECORD. 8 1/2X11 ARE
 NOT SEALED, WHITE OUT NOT ACCEPTED, NOR
 IS THE CHANGE SIGNED BY THE ARCHITECT.
  
 3)-SBC 104.2.2 ADDITIONAL INFORMATION
 SHEET A-3,ELEVATIONS DO NOT CORRALATE
 WITH THE FLOOR PLAN. WEST/ EAST ELE.
  
 4)- SHEET A-5 VS A-6 WALL SECTION HAVE
 A DISCREPANCY FOR THE FIRST FLOOR, FLOOR
 SYSTEM. IS IT STEM WALL OR MONOLITHIC?
  
 5)-SHEET A-3 DETAIL OF FRENCH DOORS &
 TRANSOM ABOVE, WHAT TYPE OF SUPPORT IS
 BETWEEN THE FRENCH DOORS AND TRANSOM
 ABOVE? HOW ARE THE ENDS TIED BACK INTO
 THE CBS STRUCTURE? THE LINTEL SCHEDULE
 DOES NOT INDICATE IF THERE IS A DOUBLE
 LINTEL IN THIS AREA?
  
 6)- SH. A-5 INDICATES A DOUBLE 2X12
 HEADER AT THE FIRST FLOOR AND THE SECOND
 FLOOR LEVELS, THE ATTACHMENT OF THE ST.
 ANGLE AT THE OUTSIDE CORNER INDICATES
 A 3X3X8X5/16" STEEL ANGLE, WHAT IS THE
 SET BACK FOR THE HOLE ATTACHMENT INTO
 THE CMU, EDGE DISTANCE VS DERATING? WHAT
 IS TO BE CONSIDERED FOR UPLIFT?
  
 7)- SHEET A-6 :
 A) SBC 1804.1.3: REQUIRES 12" FOOTING
 MIN BELOW GRADE.
 B)- SIZING OF LEDGER NOT GIVEN, WOOD
 AGAINST MASONRY / PRESSURE TREATED
 C)- ROOF FRAMING DETAIL: DOESN'T INDI-
 CATE THE LEDGER SIZE? ANCHORS OR
 SPACING?
 D)- ROOF SHEATHING THICKNESS?
 E)- SBC 2305.1.4.1. FIRE STOPPING AT
 FLOOR/ CEILING LEVELS.
  
 8)- SBC 2405.2 SAFETY GLASS REQUIRED,
 AT THE SHOWEWR ENCLOSURE.
  
 9)- SBC 2309.6 ATTIC ACCESS
 SBC 2309.7 ATTIC VENTILATION
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412
  
 WHEN PLANS ARE READY TO PERMIT THE CON-
 TRACTOR IS TO TAAKE THE PLANS TO THE
 COUNTY BUILDING DEPARTMENT FOR IMPACT
 FEES. AT THIS TIME RADON FEES ARE PAID
 TO THE CITY.