2001-03-31 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01030953
 204 MONROE DR
 W. L. SCHIELE
 762-0511
  
 1)- ENERGY FORMS NEED TO BE SIGNED BY
 THE OWNER OR AGENT THE AREA IS HIGHLIGHT
 ED.
  
 2)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 MISSING PRODUCT APPROVAL REPORTS OR
 ADDTIONAL INFORMATION REQUIRED FOR THE
 REPORTS ON HAND.
 A)- REPORT MISSING FOR THE AWNING TYPE
 WINDOW 2ND FL BATH.
 B)- FRENCH STYLE DOORS SINGLE AS WELL
 AS THE DOUBLE.
 C)- FIXED TRANSOM
 D)- MULLION FOR THE SINGLE HUNG WINDOW
 E)- ROOF TILE REPORT, SHEET A-3 NOTE
 MATCH EXISTING ROOF TILE.
 F)- STORM SHUTTER W.P.B. POLICY RE-
 QUIRES A KEY DIAGRAM AND A FASTEN-
 ING SCHEDULE FORSTORM SHUTTTERS,
 ATTACHED IS A COPY OF POLICY.
  
 3)- SBC 104.2.2 ADDITIONAL INFORMATION:
 SHEET A-3 ELEVATIONS ARE WRONG ACCORDING
 TO THE SURVEY. A-3 ARE ALSO MISSING THE
 SCUPPERS, DOWNSPOUTS & OVERFLOWS. A-1
 INDICATES THAT THE DOWNSPOUT WILL BE
 RELOCATED? WILL THE SCUPPER ALLOW THE
 WATER TO FLOW ONTO THE NEW ROOF, IS
 THERE A EXISTING OVERFLOW ALSO TO CONSID
 ER?
  
 4)- SHEET A-5 DISCREPANCY FIRST FLOOR
 FRAMING PLAN VS. A-6 WALL SECTION DEPICT
 ING A MONOLITHIC SLAB FOR THE FIRST
 FLOOR?
  
 5)- SH. A-5 DBL. 2X12 HEADER AT THE
 FIRST FLOOR AND SECOND FLOOR FL. THE
 ATTACHMENT AT THE OUTSIDE CORNER INDI-
 CATES 3X3X8X5/16 ST. ANGLE, THIS APPLICA
 TION WILL REQUIRE FLAT STEEL, ALSO INDI-
 CATE THE SETBACK FOR THE HOLE ATTACHMENT
 INTO THE CMU, EDGE DISTANCE VS. DERATING
  
 6)- SHEET A-6 :
 A) SBC 1804.1.3: REQUIRES 12" BELOW
 GRADE NOT 10".
 B) SIZING OF LEDGER NOT GIVEN, WOOD
 AGAINST CMU TO BE PRESSURE TREATED.
 C) ROOF FRAMING DETAIL: DOESN'T INDI-
 CATE THE LEDGER SIZE, ANCHORS OR
 SPACING.
 D) ROOF SHEATHING THICKNESS NOT INDI-
 CATED.
 E) SBC 2305.1.4.1. FIRESTOPPING AT
 FLOOR/ CEILING LEVELS.
  
 7)- SBC 2405.2 SAFETY GLASS REQUIRED
 AT THE SHOWER ENCLOSURE.
  
 8)- SBC 2309.6 ATTIC ACCESS
  
 9)- SBC 2309.7 ATTIC VENTILATION
  
 BUILDING PLAN REVIEW
 JIN WITMER
 (561) 659-8096 EX 8412