| 2001-03-31 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01030953 |
| | 204 MONROE DR |
| | W. L. SCHIELE |
| | 762-0511 |
| | |
| | 1)- ENERGY FORMS NEED TO BE SIGNED BY |
| | THE OWNER OR AGENT THE AREA IS HIGHLIGHT |
| | ED. |
| | |
| | 2)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | MISSING PRODUCT APPROVAL REPORTS OR |
| | ADDTIONAL INFORMATION REQUIRED FOR THE |
| | REPORTS ON HAND. |
| | A)- REPORT MISSING FOR THE AWNING TYPE |
| | WINDOW 2ND FL BATH. |
| | B)- FRENCH STYLE DOORS SINGLE AS WELL |
| | AS THE DOUBLE. |
| | C)- FIXED TRANSOM |
| | D)- MULLION FOR THE SINGLE HUNG WINDOW |
| | E)- ROOF TILE REPORT, SHEET A-3 NOTE |
| | MATCH EXISTING ROOF TILE. |
| | F)- STORM SHUTTER W.P.B. POLICY RE- |
| | QUIRES A KEY DIAGRAM AND A FASTEN- |
| | ING SCHEDULE FORSTORM SHUTTTERS, |
| | ATTACHED IS A COPY OF POLICY. |
| | |
| | 3)- SBC 104.2.2 ADDITIONAL INFORMATION: |
| | SHEET A-3 ELEVATIONS ARE WRONG ACCORDING |
| | TO THE SURVEY. A-3 ARE ALSO MISSING THE |
| | SCUPPERS, DOWNSPOUTS & OVERFLOWS. A-1 |
| | INDICATES THAT THE DOWNSPOUT WILL BE |
| | RELOCATED? WILL THE SCUPPER ALLOW THE |
| | WATER TO FLOW ONTO THE NEW ROOF, IS |
| | THERE A EXISTING OVERFLOW ALSO TO CONSID |
| | ER? |
| | |
| | 4)- SHEET A-5 DISCREPANCY FIRST FLOOR |
| | FRAMING PLAN VS. A-6 WALL SECTION DEPICT |
| | ING A MONOLITHIC SLAB FOR THE FIRST |
| | FLOOR? |
| | |
| | 5)- SH. A-5 DBL. 2X12 HEADER AT THE |
| | FIRST FLOOR AND SECOND FLOOR FL. THE |
| | ATTACHMENT AT THE OUTSIDE CORNER INDI- |
| | CATES 3X3X8X5/16 ST. ANGLE, THIS APPLICA |
| | TION WILL REQUIRE FLAT STEEL, ALSO INDI- |
| | CATE THE SETBACK FOR THE HOLE ATTACHMENT |
| | INTO THE CMU, EDGE DISTANCE VS. DERATING |
| | |
| | 6)- SHEET A-6 : |
| | A) SBC 1804.1.3: REQUIRES 12" BELOW |
| | GRADE NOT 10". |
| | B) SIZING OF LEDGER NOT GIVEN, WOOD |
| | AGAINST CMU TO BE PRESSURE TREATED. |
| | C) ROOF FRAMING DETAIL: DOESN'T INDI- |
| | CATE THE LEDGER SIZE, ANCHORS OR |
| | SPACING. |
| | D) ROOF SHEATHING THICKNESS NOT INDI- |
| | CATED. |
| | E) SBC 2305.1.4.1. FIRESTOPPING AT |
| | FLOOR/ CEILING LEVELS. |
| | |
| | 7)- SBC 2405.2 SAFETY GLASS REQUIRED |
| | AT THE SHOWER ENCLOSURE. |
| | |
| | 8)- SBC 2309.6 ATTIC ACCESS |
| | |
| | 9)- SBC 2309.7 ATTIC VENTILATION |
| | |
| | BUILDING PLAN REVIEW |
| | JIN WITMER |
| | (561) 659-8096 EX 8412 |