| 2001-07-10 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | | | | | 1- ARCHITECT TO SPECIFY CONNECTORS TO | | | SUPPORT NEW ROOF TRUSSES AT EXISTING | | | GARAGE STRUCTURE. GENERAL CONNECTOR H-10 | | | SPECIFIED ON SHEET A-8 DOESN'T APPLY TO | | | ROOF TRUSSES SITTING ON CONCRETE TIE BM. | | | | | | 2-ARCH. TO SPECIFYCONNECTOR TO RESIST | | | THE UPLIFT LOADS CALCULATED ON THE | | | ENGINEERED TRUSSES FOR THE FOLLOWING | | | TRUSSES: H7, H9, H11, H13, H15, H17, T1 | | | AND V34. | | | | | | 3-ARCHITECT'S ROOF FRAMING PLAN AND | | | TRUSS LAYOUT ARE SLIGHTLY DIFFERENT BY | | | THE GARAGE AREA. SPECIFY CONNECTORS | | | TO RESIST THE UPLIFT LOADS AT TRUSSES | | | H7A. |
|