| Date |
Text |
| 2001-03-27 00:00:00 | *************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE ELECTRICAL LEGEND, |
| | YOU SHOW THE REQ`D EGRESS LIGHTING AS |
| | CEILING J-BOXES. PLEASE SEE 210-70 FOR |
| | THE REQ`D LIGHTING FIXTURES. |
| | |
| | 2) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | PLEASE NOTE THAT MORETHAN 50% OF THE |
| | STRUCTURE IS BEING WIRED. NEED TO BRING |
| | SD REQ`MENTS UP TO CODE. |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLETS |
| | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT--ED PER 210-8-A-6. |
| | |
| | 4)NOTE: PLEASE SUBMIT PANEL SCHEDULE |
| | WITH THE REQ`D CIRCUITS SHOWN. |
| | PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. EXSITING? |
| | |
| | 6)NOTE: PLEASE SHOW ANY NEW A/C |
| | EQUIPMENT ON ELECTRICAL DRAWING. PLEASE |
| | SHOW |
| | REQ`D GFI 309.1 OF THE MECH CODE AND |
| | 210-63. PLEASE SHOW DISCONNECT(S) PER |
| | 440-11. |
| | |
| | 7)NOTE: PLEASE PLACE NOTE ON PLANS THAT |
| | AREA WHERE CLOSET MUST MAINTAIN |
| | CLEARENCE REQ`D PER 110-26 AND 384-7. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |