| Plan Review Notes For Permit 01030716 |
| Permit Number |
01030716 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-09 00:00:00 | CHECKLIST: | | | | | | 1-NEED TO FILE NOTICE OF COMMENCEMENT. | | | 2-STORM SHUTTERS: | | | -PROVIDE A KEY PLAN AND COMPLETE | | | INSTALLATION SCHEDULE. SEE CITY SAMPLE | | | -CLEARLY INDICATE ON DRAWINGS THE | | | SPECIFIC MOUNTING METHOD AND ANCHOR | | | TYPE AND SPACING TO BE USED ACCORDING | | | TO THE MEAN ROOF HEIGHT, DESIGN | | | PRESSURES, PANEL SPAN, EDGE DISTANCE, | | | CONNECTION TYPE AND STRUCTURE TO BE | | | ATTACHED TO. (WOOD OR CONCRETE BLOCK). | | | -PROVIDE PRODUCT APPROVAL FOR SHUTTERS. | | | 3-ENGINEER OF RECORD TO PROVIDE FLOOR | | | PLAN SHOWING TYPE, SIZE AND LOCATION | | | OF DOORS AND WINDOWS TO BE REPLACED IN | | | ORDER TO VERIFY COMPLIANCE WITH THE | | | EGRESS REQUIREMENTS OF SECTION 1005.4 | | | AND SAFETY GLASS REQUIREMENTS OF SEC. | | | 2405.2 OF SBC 1997. | | | 4-ENGINEER OF RECORD TO FILL OUT THE | | | DESIGN CERTIFICATION FOR BUILDING CODE | | | COMPLIANCE FORM. | | | 5-ENGINEER OF RECORD TO SPECIFY THE | | | CALCULATED DESIGN PRESSURES FOR THE | | | EXTERIOR OPENINGS AS REQUIRED BY | | | CHAPTER 16 OF SBC 1997. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT 659-8096 EXT. 8232. |
|