Plan Review Notes
Plan Review Notes For Permit 01030713
Permit Number 01030713
Review Stop E
Sequence Number 1
Notes
Date Text
2001-03-21 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PER F.A.C.
 F.S. 61G15-23.002 PLANS THAT ARE SIGNED
 AND SEALED BY AN ENGINEER MUST CONATIN
 A TITLE BLOCK W/ INFORMATION REQ`D BY
 THAT STATUE.
  
 2) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC. PLEASE NOTE THAT
 YOU SHOW"J" FOR LIGHTING REQ`D FOR
 EGRESS. ONLY ONE IS REQ`D FOR BATH, SO
 ONLY ONE NEEDS TO BE SHOWN AS A LIGHT.
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 KITCHEN WALL.
  
 4)NOTE: PLEASE NOTE THAT AS PER SCALE
 OF DRAWING. ELEC PANEL IN CLOSET DOES
 NOTMEET 110-26/384-7. ELECTRCIAL
 CLEARENCE MUST BE MET AND MAINTAINED.
 PLEASE PLACE NOTE ON PLAN THAT THE AREA
 REQ`D BY 110-26 IS DEDICATED ELECTRICAL
 SPACE.
  
 5)NOTE: PLEASE MAKE NOTE THAT IS WAS RED
 LINED ON PLAN THAT THE OUTLET ON BATH OR
 CIRCUIT FOR BATH MUST BE 20A AND #12 AWG
 PLEASE SEE 210-11-C-3 FOR SPECIFIC
 REQ`MENTS.
  
 PLEASE MAKE THE CORRECTIONS FOR NOTES
 1-4 AND NOTE #5 CAN BE ADDED TO PLAN
 OR CAN BE RELINED ON NEXT REVIEW.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372