| Date |
Text |
| 2001-03-21 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT PER F.A.C. |
| | F.S. 61G15-23.002 PLANS THAT ARE SIGNED |
| | AND SEALED BY AN ENGINEER MUST CONATIN |
| | A TITLE BLOCK W/ INFORMATION REQ`D BY |
| | THAT STATUE. |
| | |
| | 2) PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. PLEASE NOTE THAT |
| | YOU SHOW"J" FOR LIGHTING REQ`D FOR |
| | EGRESS. ONLY ONE IS REQ`D FOR BATH, SO |
| | ONLY ONE NEEDS TO BE SHOWN AS A LIGHT. |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | KITCHEN WALL. |
| | |
| | 4)NOTE: PLEASE NOTE THAT AS PER SCALE |
| | OF DRAWING. ELEC PANEL IN CLOSET DOES |
| | NOTMEET 110-26/384-7. ELECTRCIAL |
| | CLEARENCE MUST BE MET AND MAINTAINED. |
| | PLEASE PLACE NOTE ON PLAN THAT THE AREA |
| | REQ`D BY 110-26 IS DEDICATED ELECTRICAL |
| | SPACE. |
| | |
| | 5)NOTE: PLEASE MAKE NOTE THAT IS WAS RED |
| | LINED ON PLAN THAT THE OUTLET ON BATH OR |
| | CIRCUIT FOR BATH MUST BE 20A AND #12 AWG |
| | PLEASE SEE 210-11-C-3 FOR SPECIFIC |
| | REQ`MENTS. |
| | |
| | PLEASE MAKE THE CORRECTIONS FOR NOTES |
| | 1-4 AND NOTE #5 CAN BE ADDED TO PLAN |
| | OR CAN BE RELINED ON NEXT REVIEW. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |