| 2001-04-02 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01030713 | | | 1011 UPLAND RD. | | | KAISER CONSTRUCTION INC. | | | 439-0113 | | | | | | 1)- SBC 2304.1.1.3. EXISTING HEADER | | | JOIST TO BE REPLACED WITH PRESSURE TREAT | | | ED LUMBER, WOOD BEING SUBJECT TO DECAY & | | | TERMITES. | | | | | | 2)- SBC 1804.6.2.1. OPENING VENTILATION, | | | INDICATE STEM WALL VENTING TO REPLACE | | | THE VENTING CLOSED OFF BY THE SLAB ON | | | GRADE CONSTRUCTION, ALSO IS THE ACCESS | | | OR SCUTTLE HOLE STILL AVAILABLE (1804.6. | | | 2.2). | | | | | | 3)- SBC 2308.1 MISSING HEADER INFORMA- | | | TION FOR WINDOWS. | | | | | | 4)- SBC 104.2.2. ADDITIONAL INFO., THE | | | TYPICAL WALL SECTION SHOWS THE CEILING | | | JOIST & RAFTERS ATTACHED TO A LEDGER | | | WITH 3" LONG TAP CONS. THE PT LEDGER | | | WIDTH IS 1 1/2" STUCCO 5/8 "LEAVES 7/8" | | | EMBEDMENT? TAP CON ALSO DOESN'T MAKE A | | | 3" CONCRETE SCREW? | | | | | | 5)- SBC 104.2.2 ADDITIONAL INFO., ARE | | | THE WINDOWS BEING INSTALLED FLUSH WITH | | | THE EXTERIOR SHEATHING OR ARE THEY GOING | | | TO BE INSET ON BUCKS? | | | | | | 6)- MISSING THE TOP & BOTTOM PLATE | | | STRAPPING TO STUD? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|