2001-04-02 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01030713
 1011 UPLAND RD.
 KAISER CONSTRUCTION INC.
 439-0113
  
 1)- SBC 2304.1.1.3. EXISTING HEADER
 JOIST TO BE REPLACED WITH PRESSURE TREAT
 ED LUMBER, WOOD BEING SUBJECT TO DECAY &
 TERMITES.
  
 2)- SBC 1804.6.2.1. OPENING VENTILATION,
 INDICATE STEM WALL VENTING TO REPLACE
 THE VENTING CLOSED OFF BY THE SLAB ON
 GRADE CONSTRUCTION, ALSO IS THE ACCESS
 OR SCUTTLE HOLE STILL AVAILABLE (1804.6.
 2.2).
  
 3)- SBC 2308.1 MISSING HEADER INFORMA-
 TION FOR WINDOWS.
  
 4)- SBC 104.2.2. ADDITIONAL INFO., THE
 TYPICAL WALL SECTION SHOWS THE CEILING
 JOIST & RAFTERS ATTACHED TO A LEDGER
 WITH 3" LONG TAP CONS. THE PT LEDGER
 WIDTH IS 1 1/2" STUCCO 5/8 "LEAVES 7/8"
 EMBEDMENT? TAP CON ALSO DOESN'T MAKE A
 3" CONCRETE SCREW?
  
 5)- SBC 104.2.2 ADDITIONAL INFO., ARE
 THE WINDOWS BEING INSTALLED FLUSH WITH
 THE EXTERIOR SHEATHING OR ARE THEY GOING
 TO BE INSET ON BUCKS?
  
 6)- MISSING THE TOP & BOTTOM PLATE
 STRAPPING TO STUD?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412