| Plan Review Notes For Permit 01030624 |
| Permit Number |
01030624 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-04-25 00:00:00 | CHECKLIST ON PROVISO DATED 4/5/01: | | | | | | 1-ITEMS NUMBER 2,3,4,5WERE NOT DONE. | | | | | | 2-NEED TO PULL A SEPARATE PERMIT FOR | | | STORM SHUTTERS. | | | | | | 3-PROVIDE PRODUCT APPROVAL FOR: | | | -ENTRY DOORS WITH SIDELITES SINGLE | | | ASSEMBLY AS SHOWN ON ARCHITECT'S PLAN. | | | | | | 4-STOREFRONT SYSTEM DRAWINGS ARE NOT | | | LEGIBLE AND SOME SIZES SHOWN ON THE | | | PLANS ARE BIGGER THAN THE ONES | | | COVERED BY THIS PRODUCT APPROVAL. | | | NEED PRODUCT APPROVAL FOR BIGGER SIZE | | | WINDOWS ALSO. | | | -PROVIDE LEGIBLE COPIES OF THE | | | SLIDING GLASS DOORS APPROVED DRAWINGS | | | -PROVIDE PRODUCT APPROVAL FOR FIXED | | | GLASS WINDOWS WITH THE SIZE AS SHOWN | | | ON PLANS. |
|