| 2001-04-05 00:00:00 | APPROVED WITH PROVISO: |
| | |
| | 1-PROVIDE SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS. SEC. 2405.2 SBC 1997. |
| | 2-CORRECT AREA CALCULATIONS. |
| | 3-UPDATE GENERAL NOTES. WE ARE USING THE |
| | SBC 1997, NOT SFBC. |
| | 4-REVISE THE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM. SEE |
| | COMMENTS ON SUBMITTED FORM. |
| | 5-STORM PANELS UNDER A SEPARATE PERMIT: |
| | -PRODUCT APPROVAL EXPIRED. |
| | -PROVIDE A KEY PLAN AND A COMPLETE |
| | INSTALLATION SCHEDULE. |
| | -CLEARLY INDICATE ON STORM PANEL DWGS |
| | THE MOUNTING CONDITIONS AND ANCHOR |
| | TYPE AND SPACING TO BE USED ACCORDING |
| | TO THE MEAN ROOF HEIGHT, DESIGN |
| | PRESSURES, PANEL SPAN, EDGE DISTANCE, |
| | CONNECTION TYPE AND STRUCTURE TO BE |
| | ATTACHED TO (CONCRETE BLOCK). |
| | 6-PROVIDE PRODUCT APPROVAL FOR: |
| | -ENTRY DOORS WITH SIDELITES SINGLE |
| | ASSEMBLY AS SHOWN ON ARCHITECT'S PLANS |
| | -SINGLE EXTERIOR DOORS PRODUCT APPROVAL |
| | EXPIRED. |
| | -STOREFRONT SYSTEM DRAWINGS ARE NOT |
| | CLEAR AND SOME SIZES SHOWN ON THE |
| | ARCHITECTURAL DRAWINGS ARE BIGGER THAN |
| | THE ONES COVERED BY THIS PRODUCT |
| | APPROVAL. NEED PRODUCT APPROVAL FOR |
| | THOSE SIZES AS WELL. |
| | -SLIDING GLASS DOORS DRAWINGS ARE NOT |
| | LEGIBLE. |
| | -FIXED GLASS WINDOWS WITH THE SIZE |
| | SHOWN ON ARCHITECTURAL PLANS. |
| | |
| | |