| 2001-09-19 00:00:00 | THERE IS A NEED FOR SOME CODE |
| | STIPULATIONS: |
| | 1)THE DESIGN INTENT IS TO HAVE 60 |
| | TOWNHOUSE UNITS.SBC 202 DEFINES |
| | TOWNHOUSE AS A SINGLE FAMILY DWELLING |
| | CONSTRUCTED IN A SERIES OR GROUP OF |
| | ATTACHED UNITS WITH PROPERTY LINES |
| | SEPARATING EACH UNIT. |
| | |
| | THEREFORE THERE ARE 60 SEPARATE |
| | BUILDINGS, NOT "BUILDINGS A THROUGH F" |
| | |
| | 2)FIRE SPRINKLERS.TO BE ACCREDITTED |
| | FOR BUILDING CODE PURPOSES, A FIRE |
| | SPRINKLER SYSTEM MUST BE DESIGNED TO |
| | NFPA 13 - 96. 13R AND 13D ARE NOT |
| | RECOGNIZED ALTERNATES.SEE SBC 903.2, |
| | (THE LAST SENTENCE, PARTICULARLY) AND |
| | TABLE 500 FOOTNOTE D. |
| | |
| | AS GROUP R3, (SINGLE FAMILY DWELLINGS) |
| | THEY WILL REQUIRE A FULL 13 SYSTEM ONLY |
| | IF THEY ARE 3 STORY AND TYPE VI OR V |
| | UNPROTECTED, SEE FOOTNOTE H TABLE 500. |
| | |
| | INARGUABLY, THE 13D AND 13R SYSTEMS ARE |
| | BENEFICIAL, HOWEVER IN NO WAY SHOULD |
| | THEY BE CONSIDERED AN EQUAL AND |
| | ALTERNATE FOR BUILDING CODE PURPOSES. |
| | |
| | PLEASE REFER TO THE EARLIER CODE |
| | COMMENTS AS SOME OF THEM STILL PERTAIN |
| | AND MUST BE COMPLIED WITH PRIOR TO |
| | OBTAINING PERMITS. |