| Plan Review Notes For Permit 01030614 |
| Permit Number |
01030614 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-09-13 00:00:00 | 1) FIRE UNDERGROUND LINE PLAN DISPLAYS | | | BUILDING FIRE DEPARTMENT CONNECTIONS | | | BUT THE NOTES ON THE SAME PAGE STATES | | | THAT A SINGLE 1/2 FDC SHALL BE PROVIDED | | | AT EACH UNIT. PLEASE CORRELATE | | | INFORMATION. ALSO ONLY SINGLE 2 1/2 | | | CONNECTIONS WILL BE ALLOWED. | | | 2) ACCORDING TO DOCUMENTS, EACH UNIT | | | WILL HAVE A SECURITY SYSTEM THAT WILL | | | BE TIED INTO THE FLOW AND TAMPER | | | SWITCHES. HOW DOES THIS WORK AND THERE | | | APPEARS TO BE SOME CONFUSION REGARDING | | | THIS MATTER. THE FIRE SPRINKLER SYSTEMS | | | ARE REQUIRED SO THIS MEANS THAT THE | | | FIRE SPRINKLER MONITORING IS THEREFORE | | | REQUIRED. WHAT HAPPENS IF A TENANTS | | | SECURITY IS OUT OF SERVICE OR THE | | | SECURITY SYSTEM IS DISCONTINUED. WHAT | | | CODE PROVISIONS ALLOWS THIS ARRANGEMENT | | | AND HOW DOES IF AFFECT LISTING OF | | | EQUIPMENT. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|