Plan Review Notes
Plan Review Notes For Permit 01030614
Permit Number 01030614
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2001-09-13 00:00:001) FIRE UNDERGROUND LINE PLAN DISPLAYS
 BUILDING FIRE DEPARTMENT CONNECTIONS
 BUT THE NOTES ON THE SAME PAGE STATES
 THAT A SINGLE 1/2 FDC SHALL BE PROVIDED
 AT EACH UNIT. PLEASE CORRELATE
 INFORMATION. ALSO ONLY SINGLE 2 1/2
 CONNECTIONS WILL BE ALLOWED.
 2) ACCORDING TO DOCUMENTS, EACH UNIT
 WILL HAVE A SECURITY SYSTEM THAT WILL
 BE TIED INTO THE FLOW AND TAMPER
 SWITCHES. HOW DOES THIS WORK AND THERE
 APPEARS TO BE SOME CONFUSION REGARDING
 THIS MATTER. THE FIRE SPRINKLER SYSTEMS
 ARE REQUIRED SO THIS MEANS THAT THE
 FIRE SPRINKLER MONITORING IS THEREFORE
 REQUIRED. WHAT HAPPENS IF A TENANTS
 SECURITY IS OUT OF SERVICE OR THE
 SECURITY SYSTEM IS DISCONTINUED. WHAT
 CODE PROVISIONS ALLOWS THIS ARRANGEMENT
 AND HOW DOES IF AFFECT LISTING OF
 EQUIPMENT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910